TCI-W Universal Controller
OVERVIEW
Doc: 70-00-0158, V1.4-20220321 © Vector Controls GmbH, Switzerland Page 1
Subject to alteration
TCI-W Universal Controller
Features
• Universal PID and/or binary control for any analog
input/output signal and range.
• Multiple auxiliary functions: heat-cool auto changeover,
automatic enable, setpoint compensation.
• Differential, averaging, min and max functions
• Cascading of control loops (-W22 type).
• Alarm monitoring of low and high limits on all inputs.
• Programmable reaction in case of alarm.
• Feedback function for inputs and set points.
• Functions for dehumidifying, set point shift, cascade
control.
• Password protected programmable user and control
parameters.
TCI-W22 also includes
• Power Cap protected real-time clock with 48hr power
backup.
• 7-day programmable schedules, with options including
change of setpoints and direct position of manual
outputs.
• Blue backlight.
• Fan coil units
• Heat exchangers
• Zoning
• VAV
• Air handlers
• Fan, Pump control
• Humidifiers
• Dehumidifiers
• Ventilation
• Radiant heating
• Radiant cooling
• Pressurization
General
• TCI-W11: 1 independent control loop, 1 internal temperature sensor, 1 universal input (analog/binary/temp), 2
binary outputs, 1 analog output
• TCI-W22: 2 independent control loops, 1 internal temperature sensor, 2 universal inputs, 2 binary outputs, 1
analog output.
• Internal temperature sensor standard. Add replaceable humidity element as required: AES3-HT-A2 (2%), AES3-
HT-A3 (3%), or AES3-HT-A5 (5%)
• Flexible application configuration is made with a parameter-setting routine using the standard operation terminal.
Name
Ordering
Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy:SDB-Tn10-20 (duct), SRA-Tn10
(room), SDB-Tn10-20 + AMI-S10 as immersion sensor.
Actuators: Choose modulating actuators with an input signal type of 0-10 V DC or 4-20 mA (Min. and max.signal
limitations may be set with parameters.3-pointpoint actuators with constant running time are recommended.
Binary auxiliary devices (e.g. pumps, fans, on/off valves, humidifiers, etc):Do not directly connect devices that exceed
specified limits in technical specifications – observe startup current on inductive loads.
Housing Blank = square housing
In/Outputs: See table below
Control loops: 1 = 1 control loop, 2 = 2 control loops
Mounting: W = Wall mounted
Series: TCI