EasyManuals Logo
Home>Vector>Controller>TCI-W

Vector TCI-W User Manual

Vector TCI-W
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
TCI-W11, TCI-W22 Universal Controller
OUTPUT CONFIGURATION
Doc: 70-00-0158C, V2.0-20220523 © Vector Controls GmbH, Switzerland Page 15-22
Subject to alteration
Output configuration
Analog output configuration (1A)
Parameter
Description
Range
Default
1A 00
Select control loop or special function (0= OFF):
1= LP1, 2= LP2
3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct)
4= Manual positioning or by time schedule (0100%)
5= Transmit value of an input
05
1
1A 01
When 1A00 = 1configure output:
0= Heating/reverse
1= Cooling/direct
2= Heating and cooling (2 pipe)
3= Transmit setpoint
When 1A00 = 4 Manual positioning or time schedule controlled
0 = time schedule only
1 = manual positioning and by time schedule
When 1A00 = 5, select input (0= function disabled):
1= 1T, 2= 1H, 3= 1U, 4= 2U
04
0
1A 02
Type of output signal: OFF= 010V, 020mA, ON= 210V, 420mA
ON/OFF
OFF
1A 03
Minimum limitation of output signal default and in loop heating mode
0100%
0
1A 04
Maximum limitation of output signal default and in loop heating mode
0100%
100%
1A 05
Minimum limitation of output signal in loop cooling mode
0100%
0%
1A 06
Maximum limitation of output signal in loop cooling mode
0100%
100%
1A 07
Choose alarm to set output to 100% (output 0%on conflicting alarms)

Alarm: 1 2 3 4 5 6 7 8
ALA1ALA8

1A 08
Choose alarm to set output to 0%. (output 0% on conflicting alarms)

Alarm: 1 2 3 4 5 6 7 8
ALA1ALA8

1A 09
Transmit value (1A00=5): minimum input value
per input
0°C
1A 10
Transmit value (1A00=5): maximum input value
per input
100°C
Set jumpers on the back of the controller: 010 VDC (default), or 020 mA. Further define analog outputs with
A02.Custom ranges can be created by setting minimum and maximum signal limits.
A control loop, special function, digital control or analog control sequence is not active until it is assigned an output.
Low and high limit alarms are defined with input parameters. With output parameters assign an
alarm to an output and select output state. The required output for each alarm can be
individually selected. Multiple alarms can be signed to one output. If one alarm is selected to
simultaneously activate and deactivate an output, the one to de-activate has precedence.
With manual positioning (1A00=4) position the output by time schedule or directly in 0.5%
steps. Setting 1A01 to 0 will disable manual positioning. The output will then only be controlled by time schedule.
With dehumidifying (1A00=3) the maximum value is taken of cooling and dehumidifying. When the humidity is too
high, cooling will continue to operate, even without a demand for cooling, to dehumidify the air and heating will
activate to maintain comfort.
Input values of inputs and set points of control loops may be transmitted on the analog outputs.
Minimum or maximum limits of output signals may be reversed. This allows to create a control option for
example of 6-way valves where the following conditions are required: 0% full cooling, 50% no cooling or heating,
100% full heating. This is achieved by setting 1A05 = 50%, 1A06 = 0%, 1A03 = 50% and 1A04 = 100%.
While one sequence is reversed and the other is direct, the output will remain in OFF mode at the percentage defined
with the last active minimum sequence.
Note: Alarm values will not be affected by minimum or maximum limits.
For VAV Function individual minimum and
maximum limits may be assigned for cooling and
heating. In VAV applications maximum cooling
output matches the maximum air volume the
VAV box is set to deliver. As demand for airflow
in cooling mode decreases, airflow dwindles until
it reaches minimum cooling output (1A05). This
minimum will be based on the airflow needed at
design cooling and is typically 10% to 15% of
maximum cooling airflow. When this minimum is
reached the system is in dead-band neither
heating nor cooling. Minimum airflow in heating
mode is set with 1A03. As the system moves into heating mode, heating airflow increases until it reaches the
maximum heating output (1A04), typically 30 to 50% of maximum cooling airflow.
W
H
W
C
100
50
0
Y
H1
,Y
R1
X
DZ
Y
C1,
Y
D1
Heating
Cooling
1A04
1A05
1A03
1A06
T (°C/F), U(V, mA)
Output Priority
1. Alarm level low
2. Alarm level high
3. Operation mode OFF
4. Control function

Other manuals for Vector TCI-W

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vector TCI-W and is the answer not in the manual?

Vector TCI-W Specifications

General IconGeneral
BrandVector
ModelTCI-W
CategoryController
LanguageEnglish

Related product manuals