X2-OPERATIONS MANUAL BUTTON DISPLAY
Doc: 70-00-0950A, Serie X2, 20211220 © Vector Controls GmbH, Schweiz Page 10-16
Subjects to alteration www.vectorcontrols.com
6. Press the ( / ) button and assign one of the following functions
to the program with the ( ) ( ) button:
Switching time not activated
Operating mode ON (Occupied), ECO (Unoccupied) or OFF
(protective operation)
Setpoint of a control loop (setting range 0-100%, °C/°F,
Pascal)
Positioning of the analog output (output must be in
manual mode!)
Fan control (fan stages from FSP0-3 and Auto)
Positioning of the digital output (output must be in
manual mode!)
Annual time schedule. (holidays)
➔ 1 bar indicates setting step 1 is executed.
…
For setting a holiday "Hday" see
chapter 5.3.3
7. Press the ( / ) button and adjust the time from 00:00…23:45 in
15 minutes steps with the ( ) ( ) button.
➔ 2 bars indicate setting step 2 is executed.
8. Press the ( / ) button to select Monday (Day 1).
9. Press the ( ) button to execute the program on Monday (Day 1).
➔ A triangle symbol is displayed above the 1.
➔ 3 top bar symbols are displayed.
10. Press the ( ) button to not execute the program on Monday
(Day 1).
➔ The triangle symbol above the 1 disappears.
➔ The 3 top bar symbols disappear.
11. Press the ( / ) button to go to the next day.
➔ DAY1 (Day 1) and Pr01 (Program 1) is displayed in this
example.
➔ 3 bars indicate setting step 3 is executed.
12. Repeat this process to set DAY2 to DAY7 (Tuesday to Sunday).
➔ Triangle symbol indicate the days of the week the program will be
executed.
13. Set the action to be performed by pressing the ( ) ( ) and
( / ) button depending on function selected in instruction No. 5:
a. OP (operating mode):
ON = Occupied, normal operation
ECO = Unoccupied, reduced operation
OFF = protective operation
b. LP (control loop set point) LP01-LP0x*:
°C/°F
c. AO (analogue output position) Ao01-Ao0x**:
0-100%
d. FAN (fan control, fan speed) FAN1-FAN2:
fan speed 0-3 (FSP0-FSP3)
Auto mode (Auto)
e. do (digital output position) do01-do0x***:
ON = enabled
OFF = disabled
➔ 4 and 5 bars indicate setting step 4 rep. 5 is executed.
* The number of available control loops depends on the used X2-controller.
** The number of available analogue outputs depends on the used X2-
controller.
*** The number of available digital outputs depends on the used X2-
controller.