X2-OPERATIONS MANUAL BUTTON DISPLAY
Doc: 70-00-0950A, Serie X2, 20211220 © Vector Controls GmbH, Schweiz Page 10-16
Subjects to alteration www.vectorcontrols.com
VECTOR
6. Press the ( / ) button and assign one of the following functions
to the program with the ( ) ( ) button:
no
=
Switching time not activated
OP
=
Operating mode ON (Occupied), ECO (Unoccupied) or OFF
(protective operation)
LP
=
Setpoint of a control loop (setting range 0-100%, °C/°F,
Pascal)
AO
=
Positioning of the analog output (output must be in
manual mode!)
FAN
=
Fan control (fan stages from FSP0-3 and Auto)
do
=
Positioning of the digital output (output must be in
manual mode!)
Hday
=
Annual time schedule. (holidays)
1 bar indicates setting step 1 is executed.
For setting a holiday "Hday" see
chapter 5.3.3
7. Press the ( / ) button and adjust the time from 00:00…23:45 in
15 minutes steps with the ( ) ( ) button.
2 bars indicate setting step 2 is executed.
8. Press the ( / ) button to select Monday (Day 1).
9. Press the ( ) button to execute the program on Monday (Day 1).
A triangle symbol is displayed above the 1.
3 top bar symbols are displayed.
10. Press the ( ) button to not execute the program on Monday
(Day 1).
The triangle symbol above the 1 disappears.
The 3 top bar symbols disappear.
11. Press the ( / ) button to go to the next day.
DAY1 (Day 1) and Pr01 (Program 1) is displayed in this
example.
3 bars indicate setting step 3 is executed.
12. Repeat this process to set DAY2 to DAY7 (Tuesday to Sunday).
Triangle symbol indicate the days of the week the program will be
executed.
13. Set the action to be performed by pressing the ( ) ( ) and
( / ) button depending on function selected in instruction No. 5:
a. OP (operating mode):
ON = Occupied, normal operation
ECO = Unoccupied, reduced operation
OFF = protective operation
b. LP (control loop set point) LP01-LP0x*:
°C/°F
c. AO (analogue output position) Ao01-Ao0x**:
0-100%
d. FAN (fan control, fan speed) FAN1-FAN2:
fan speed 0-3 (FSP0-FSP3)
Auto mode (Auto)
e. do (digital output position) do01-do0x***:
ON = enabled
OFF = disabled
4 and 5 bars indicate setting step 4 rep. 5 is executed.
* The number of available control loops depends on the used X2-controller.
** The number of available analogue outputs depends on the used X2-
controller.
*** The number of available digital outputs depends on the used X2-
controller.
OP