2 Vac Sensor Installation Epoxy Sealing Vac System Field Wiring Connections
2-12
Figure 2-15.- Epoxy Sealing Wiring Connections
consoles\epxy3warn.eps
To console
To sensor
Tie wrap
Wire nuts
ACB
Make sure that
the ends of cable
sheathing are
sub-merged in
sealant
1. Open epoxy sealant package, and remove resin pack.
2. Holding resin pack as shown in A, bend pak along long length.
3. As shown in B, firmly squeeze the RED SIDE of the resin, forcing it
through the center seal and into BLACK SIDE.
4. Mix thoroughly to a uniform color by squeezing contents back and
forth 25-30 times.
5. Squeeze mixed, warm resin into one end of pack and cutoff other
end.
6. Slowly insert wiring connections into sealing pack until they fit
snugly against the opposite end as shown in C.
7. Twist open end of bag and use tie wrap to close it off and position
the tie wrapped end up until the resin jells.
Epoxy sealant is irritating to eyes, respiratory system, and skin.
Can cause allergic skin reaction. Contains: epoxy resin and
Cycloaliphatic epoxycarboxylate.
Precautions: Wear suitable protective clothing, gloves, eye, and
face protection. Use only in well ventilated areas. Wash
thoroughly before eating, drinking, or smoking.
CAUTION
NOTICE
NOTICE
When temperature is below 50°F (10°C), keep resin
in a warm place prior to mixing (e.g., in an inside
pocket next to body).
Instructions