5 Vac System Field Wiring - TLS-450PLUS Console Connecting Pump Control to TLS-450PLUS Console
5-2
FOR SITES WITHOUT PLLD LEAK DETECTION
An IOM module is required in the TLS Console for Vac Sensor pump control if there is no PLLD. Refer to Figure 5-
2 for Red Jacket pump control wiring and to Figure 5-3 for non-Red Jacket pump control wiring.
Figure 5-2.- Red Jacket STP Control And Pump Sense Inputs
Pump In
Pump Return
WARNING
OFF
DISCONNECT, LOCK OUT, AND TAG POWER
TO THE STP/SELF SERV SYS./DISPENSER
AT THE POWER PANEL BEFORE CONNECTING
WIRING TO THIS EQUIPMENT.
WARNING
OFF
Power Panel
110 Vac
AC Neutral
Self-Serve System
or Dispenser switched
hot 120 Vac
Pump Control
Power Panel
From
Beaker Panel
Pump Power
To
Submersible
Pump
Product
Relay
Red Jacket
Remote Control Box
M2 M1 N L1 L2
S2
Rigid Conduit (enters Console
through a Power Bay knockout)
RTN
12V
1
2
3
4
1
2
3
4
5
1
2
3
4
5
RTN
12V
RTN
12V
RTN
12V
Maximum AC
Input Ratings
120/240 Vac, 0.10 A
Maximum Relay Contact Ratings
120/240 Vac 5A, 30 Vdc 5A
Fuse Ratings 5A, 250 Vac Type T (Slo-Blo)
Maximum External Contact
Closure Circuit Ratings
12 Vdc, 0.015 A

Table of Contents

Other manuals for Veeder-Root TLS-350R PLUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-350R PLUS and is the answer not in the manual?

Veeder-Root TLS-350R PLUS Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-350R PLUS
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals