EGH Gas-firEd boilErs — sEriEs 4 — boilEr manual
Table 12 Service and maintenance schedules (service technician and owner)
Follow the “Service and maintenance” procedures given throughout this manual, the Control Supplement and in com-
ponent literature shipped with the boiler. See “Read this page first” on page 2. Failure to perform the service and main-
tenance could result in damage to the boiler or system. Failure to follow the directions in this manual and component
literature could result in severe personal injury, death or substantial property damage.
Service technician
(see following pages for instructions)
Owner maintenance
(see User’s Information Manual for instructions)
ANNUAL START-UP
❏ Inspect:
• Reported problems
• Boiler area
• Air openings
• Flue gas vent system
• Pilot and main burner flames
• Piping
• Boiler heating surfaces
• Burners and base
❏
Service:
• Gauge glass
❏
Start-up:
• Perform start-up per manual
❏
Check/test:
• Gas piping
• Boiler waterline
• Limit controls and cutoffs
• Boiler relief valve
❏
Review:
• Review with owner
❏ Daily • Check boiler area
• Check boiler pressure gauge
• Check air openings
❏ Monthly • Check boiler and system piping
• Check venting system
• Check/operate boiler relief valve
• Check pilot and main burner flames
❏ Periodically • Test low water cutoff
❏ End of season • Shut down procedure
Service and maintenance
Label all wires prior to disconnection when servic-
ing controls. Wiring errors can cause improper and
dangerous operation.
To avoid personal injury, death or property damage,
keep boiler area clear and free from combustible
materials, gasoline and other flammable vapors
and liquids.
Do not block flow of air to boiler. Incomplete
combustion and flue gas spillage can occur.
Do not store sources of hydrocarbons (i.e., bleaches,
cleaners, chemicals, sprays, paint removers, fabric
softeners, etc.) in boiler area. This can contribute
to shortened boiler/vent system life.