Connecting Wiring Check Adapters
Connect the wiring check adapters to detect disconnected or short-circuited eld wiring between
the digital input module and eld equipment. These adapters should be connected at the eld
equipment side. The two types of these adapters are:
SCB100: Disconnection detection while accepting an OFF signal
If this type of adapter is connected in parallel with a sensor switch, a disconnection occurring
while accepting an OFF signal can be detected.
SCB110: Short-circuit detection
If this type of adapter is connected in series with a sensor switch, a short-circuit in the power
line, occurring while accepting an ON signal, or a short-circuit with other channels can be
detected. In addition to the above wiring check adapters, input module’s diagnostic functions
should be able to detect disconnections or short-circuits.
SEE
ALSO
For more information about diagnostic features of the input modules, see the following:
Appendix 1.3.4 “Setting for the DI channel” of the Engineering Guide Vol. 1 (IM 32P01C10-01EN).
Shape of Wiring Check Adapters
The following gure shows the shape of the SCB100 and SCB110.
F030620.ai
Figure External View of SCB100 and SCB110
Connecting Wiring Check Devices
F030621.ai
DCn
INn
SDV144
SCB100
Detect disconnection
when input is OFF
Detect short circuit
when input is ON
Detect disconnection
and short circuit
DCn
INn
SDV144
SCB110
DCn
INn
SDV144
Red
Blue
Red
Blue
SCB100
SCB110
: The field equipment switch
Figure Connecting Wiring Check Adapters
IMPORTANT
Connect the SCB110 with correct polarity. If it is connected incorrectly, no detection can be
made.
To detect short-circuits or disconnections in the eld wiring e󰀨ectively, locate the adapters
in the vicinity of the eld equipment. Also install these adapters in a location out of direct
sunlight and sheltered from rain.
Be careful not to bend a covered part.

Other manuals for YOKOGAWA ProSafe-RS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ProSafe-RS and is the answer not in the manual?

YOKOGAWA ProSafe-RS Specifications

General IconGeneral
BrandYOKOGAWA
ModelProSafe-RS
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals