3. Cabling
3-80
TI 32P01J10-01EN
3.8.3 N-ESB Bus
The following gure shows a connection example of the N-ESB bus.
Connect UTP straight Cable of Cat5e (two) from N-ESB bus Coupler Module (S2EN402,
S2EN404) to N-ESB bus Module (S2EN501).
F030807.ai
S2SC70D
S2EN404
S2EN501
Bus1 Bus2
UTP of Cat 5e
RJ45
Base Plate for Node
Interface Unit
S2EN501-S00
Base Plate for Node
Interface Unit
N-ESB Bus
Bus1
Bus2
-S00
-S01
-S02
N-ESB Bus
Figure Example of N-ESB Bus Connection
IMPORTANT
An N-ESB bus cable for the ProSafe-RS can be routed only in the cabinet or within the cabinets
bayed together. An optical ESB bus cable must be used instead of an N-ESB bus cable when a
cable is routed outside of the cabinet.
June 30, 2017-00