2. Transportation, Storage and Installation
2-7
TI 32P01J10-01EN
2.5.1 Installation on Floor
The installation method varies with the type of the oor and building.
• After unpacked, be careful not to put any impact until the equipment is xed to the oor to
prevent it from falling to the oor.
• Install devices as specied in the plans. Check the position of front and back panels of the
cabinet.
Avoid physical shock. Never use hammers.
• Fix each equipment to the oor.
The explanation below shows how to x devices on dierent types of oors.
Concrete Floor
Clamp the equipment to the oor using anchor bolts. It is recommended to use M12 bolts and
3200 N•cm (320 kgf•cm) tightening torque.
Equipment
Figure Using Anchor Bolts
Steel Floor
Clamp the equipment to the oor using clamp bolts.
After cabling through the riser duct, ll the duct with rubber sponges and seal the top with putty.
Equipment
Steel floor
Clamp bolt
Duct
Riser
Figure Using Clamp Bolts
Nov. 27, 2015-01