Page #76 background image
2. Transportation, Storage and Installation
2-18
TI 32P01J10-01EN
Terminal Board and Relay Board Mounting Directions
Mount a terminal board and a relay board in the directions as shown in the below gure.
When mounting SBD2D in the direction of b or c, the following conditions must be met.
When the ambient temperature is 60 °C or lower, the total load current of the SBD2D must
be kept within the specied value of 8 A or lower.
When the ambient temperature is at 70 °C, the total load current must be 6 A or lower.
In case the ambient temperature is in between 60 and 70 °C, reduce the total load current
from 8 A maximum by the rate of 0.2 A/°C.
DIN rail
Direction a Direction b Direction c
F020511.ai
Oct. 25, 2016-00