EasyManuals Logo

York ECO2 YPAL 050 User Manual

York ECO2 YPAL 050
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background image
24
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
Installation
PHYSICAL DATA (CONTINUED)
TABLE 2-6 – PHYSICAL DATA - COMPRESSORS
COMPRESSORS UTILIZED COMPRESSOR NOMINAL TONS
CAPACITY %
SYSTEM 1 SYSTEM 2 SYSTEM 1 SYSTEM 2
“COMPR
# 1”
“COMPR
# 2”
“COMPR
# 3”
“COMPR
# 4”
“COMPR
# 1”
“COMPR
# 2”
“COMPR
# 3”
“COMPR
# 4”
“STAGE
1”
“STAGE
2”
“STAGE
3”
“STAGE
4”
MODEL
050 ZP137 ZP120 ZP137 ZP120 13.58 12.53 13.58 12.53 26.0 52.0 76.0 100.0
051 ZP137 ZP137 ZP137 ZP137 13.58 13.58 13.58 13.58 25.0 50.0 75.0 100.0
060 ZP182 ZP137 ZP182 ZP137 17.95 13.30 17.95 13.30 28.7 57.4 78.7 100.0
061 ZP182 ZP137 ZP182 ZP154 17.95 13.30 17.60 14.86 28.2 55.8 76.7 100.0
TABLE 2-5 – PHYSICAL DATA - 050-061 MODELS (CONTINUED)
UNIT SIZE 050 051 060 061
FILTERS - 2” PLEATED, 30% EFFICIENT (PRE-FILTER POSITION)
QUANTITY 8 / 12 8 / 12 8 / 12 8 / 12
SIZE (LENGTH X WIDTH) (IN.) 25X16 / 25X20 25X16 / 25X20 25X16 / 25X20 25X16 / 25X20
TOTAL FILTER FACE AREA (SQUARE FEET) 63.9 63.9 63.9 63.9
FILTERS -12” RIGID 65%, 2” 30% PREFILTER (PRE-FILTER POSITION)
QUANTITY 1 / 4 / 9 1 / 4 / 9 1 / 4 / 9 1 / 4 / 9
SIZE (LENGTH X WIDTH) (IN.)
16X20/25X16/
25X20
16X20/25X16/
25X20
16X20/25X16/
25X20
16X20/25X16/
25X20
TOTAL FILTER FACE AREA (SQUARE FEET) 43.0 43.0 43.0 43.0
FILTERS -12” RIGID 95%, 2” 30% PREFILTER (PRE-FILTER POSITION)
QUANTITY 1 / 4 / 9 1 / 4 / 9 1 / 4 / 9 1 / 4 / 9
SIZE (LENGTH X WIDTH) (IN.)
16X20/25X16/
25X20
16X20/25X16/
25X20
16X20/25X16/
25X20
16X20/25X16/
25X20
TOTAL FILTER FACE AREA (SQUARE FEET) 44.6 44.6 44.6 44.6
FILTERS - 2” CARBON (PRE-FILTER POSITION)
QUANTITY 8 / 12 8 / 12 8 / 12 8 / 12
SIZE (LENGTH X WIDTH) (IN.) 25X16 / 25X20 25X16 / 25X20 25X16 / 25X20 25X16 / 25X20
TOTAL FILTER FACE AREA (SQUARE FEET) 63.9 63.9 63.9 63.9
FILTERS - 12” RIGID 95% IN POST-FILTER POSITION
QUANTITY 1 / 3 / 9 1 / 3 / 9 1 / 3 / 9 1 / 3 / 9
SIZE (LENGTH X WIDTH) (IN.)
16X20/25X16/
25X20
16X20/25X16/
25X20
16X20/25X16/
25X20
16X20/25X16/
25X20
TOTAL FILTER FACE AREA (SQUARE FEET) 41.8 41.8 41.8 41.8
GAS FURNACES
STAGED FURNACE SIZES (INPUT/OUTPUT/STEPS)
375 MBH / 300 MBH / 1 STEP
750 MBH / 600 MBH / 2 STEPS
1125 MBH / 900 MBH / 3 STEPS
GAS PRESSURE RANGE 4.5-13.5" WC 4.5-13.5" WC 4.5-13.5" WC 4.5-13.5" WC
AIRFLOW RANGE
(MIN HEATING)
375 MBH 7,500 7,500 11,500 11,500
750 MBH 14,000 14,000 14,000 14,000
1125 MBH 21,000 21,000 21,000 21,000
MINIMUM OA TEMP FOR MECH. CIG. 40.0 °F 40.0 °F 40.0 °F 40.0 °F
LOW AMBIENT OPTION MIN. OA TEMP 0.0 °F 0.0 °F 0.0 °F 0.0 °F

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York ECO2 YPAL 050 and is the answer not in the manual?

York ECO2 YPAL 050 Specifications

General IconGeneral
BrandYork
ModelECO2 YPAL 050
CategoryAir Conditioner
LanguageEnglish

Related product manuals