EasyManuals Logo
Home>York>Air Conditioner>ECO2 YPAL 050

York ECO2 YPAL 050 User Manual

York ECO2 YPAL 050
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
31
2
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
TABLE 2-14 – ELECTRIC HEAT
TABLE 2-15 – AIRFLOW AND ENTERING AIR/AMBIENT LIMITATIONS
* Cooling Only Units
KW
NOMINAL VOLTAGE
208/3/60
AMPS
230/3/60
AMPS
460/3/60
AMPS
575/3/60
AMPS
40 96 96 48 40
80 193 193 96 80
108 260 260 130 109
150 181 151
Limitations Model Size
50 51 60 61
Minimum
Airflow at
Standard Design
Conditions.
CFM*
(min to max)
10000 -
22500
10000 -
22500
12500 -
24000
12500 -
24000
Entering Wet
Bulb Temp F°
(min/max)
57/75 57/75 57/75 57/75
Entering Dry
Bulb Temp F°
(min/max)
68/90 68/90 68/90 68/90
Ambient Temp F°
without Low
Amb option
50/120 50/120 50/120 50/120
Ambient Temp F°
with Low Amb
option
0/120 0/120 0/120 0/120
ELECTRIC DATA (CONTINUED)