4
FIG. 4-7 – ECCENTRIC CAM LOCKING COL LAR
Do not apply excessive force to the
bear ing hous ing (pillow block or
bear ing hous ing (pillow block or
fl ange) when installing the bearing
fl ange) when installing the bearing
1. Torque screw “A” to 1/2 rec om mend ed torque.
2. Torque screw “B” to full min. recommended
3. Torque screw “A” to full rec om mend ed value.
After proper installation of the
bearing(s), run the unit for 10 to 15
minutes. Shut the unit down and lock
it out. Check for proper en gage ment
of locking col lar and tight ness of set
When replacing split bearings, refer to manufacturer’s
instruction provided with the bearing.
important to ensure that proper radial clearances are
observed between the roller bearings and outer face.
Failure to make proper adjustments will cause pre ma ture
TABLE 4-2 – SET SCREW TORQUE
5 - 7