246824-YTG-G-1208
Johnson Controls Unitary Products 55
115°F 125°F
1875
77 88.3 9.2 32.2 27.8 20.0 - - - 80.3 10.2 26.0 24.0 16.6 - - -
72 81.1 9.1 49.8 41.9 34.1 26.3 - - 73.8 10.1 46.1 38.5 30.9 23.3 - -
67 74.0 9.1 67.3 56.1 48.2 40.4 32.6 - 67.3 10.0 65.7 52.7 45.1 37.5 29.9 -
62 69.6 9.0 69.6 69.6 57.9 50.1 42.3 34.5 64.5 10.0 64.5 64.5 53.2 45.6 38.0 30.4
2250
77 89.8 9.3 39.9 30.9 21.9 - - - 81.1 10.2 35.8 27.1 18.3 - - -
72 82.6 9.2 55.3 46.4 37.4 28.4 - - 74.5 10.1 51.5 42.7 34.0 25.2 - -
67 75.3 9.1 70.8 61.8 52.9 43.9 34.9 - 68.0 10.0 67.2 58.4 49.6 40.9 32.1 -
62 70.8 9.1 70.8 70.8 63.4 54.5 45.5 36.5 65.2 10.0 65.2 65.2 58.6 49.9 41.1 32.3
57 70.3 9.1 70.3 70.3 63.9 54.9 46.0 37.0 64.5 10.0 64.5 64.5 58.1 49.4 40.6 31.8
2625
77 91.4 9.3 47.5 34.0 23.8 - - - 81.9 10.2 45.6 30.2 20.0 - - -
72 84.0 9.2 60.9 50.8 40.6 30.5 - - 75.3 10.1 56.9 47.0 37.1 27.2 - -
67 76.6 9.1 74.3 67.6 57.5 47.3 37.2 - 68.7 10.1 68.7 64.1 54.2 44.3 34.3 -
62 72.0 9.1 72.0 72.0 69.0 58.8 48.7 38.5 65.9 10.0 65.9 65.9 64.0 54.1 44.1 34.2
57 71.5 9.1 71.5 71.5 69.5 59.4 49.2 39.1 65.2 10.0 65.2 65.2 63.5 53.6 43.6 33.7
3000
77 92.9 9.3 55.1 37.0 25.7 - - - 82.7 10.2 55.4 33.3 21.7 - - -
72 85.4 9.2 66.5 55.2 43.9 32.6 - - 76.0 10.2 62.4 51.3 40.2 29.1 - -
67 77.9 9.2 77.9 73.4 62.1 50.8 39.5 - 69.3 10.1 69.3 69.3 58.7 47.7 36.6 -
62 73.3 9.1 73.3 73.3 74.5 63.2 51.9 40.6 66.5 10.1 66.5 66.5 66.5 58.3 47.2 36.1
57 72.7 9.1 72.7 72.7 75.1 63.8 52.5 41.2 65.9 10.0 65.9 65.9 65.9 57.7 46.7 35.6
3375
72 85.2 9.2 71.0 58.8 46.6 34.5 - - 75.5 10.2 66.4 54.5 42.6 30.7 - -
67 77.7 9.2 77.7 75.4 65.9 53.8 41.6 - 68.9 10.1 68.9 68.9 62.2 50.3 38.4 -
62 73.1 9.1 73.1 73.1 73.7 61.5 49.3 37.1 66.1 10.1 66.1 66.1 66.1 55.6 43.7 31.8
57 72.6 9.1 72.6 72.6 73.7 61.5 49.4 37.2 65.4 10.1 65.4 65.4 65.4 55.0 43.1 31.2
3750
72 85.0 9.3 75.5 62.4 49.4 36.3 - - 75.0 10.2 70.4 57.7 45.0 32.3 - -
67 77.5 9.2 77.5 77.5 69.8 56.7 43.7 - 68.4 10.1 68.4 68.4 65.7 53.0 40.3 -
62 72.9 9.1 72.9 72.9 72.9 59.8 46.8 33.7 65.6 10.1 65.6 65.6 65.6 52.9 40.2 27.5
57 72.4 9.1 72.4 72.4 72.4 59.3 46.2 33.2 65.0 10.1 65.0 65.0 65.0 52.3 39.6 26.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
XP090 (7.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65