246824-YTG-G-1208
Johnson Controls Unitary Products 69
ZR120 (10 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive Standard 2 HP & Drive Hi Static 3 HP & Drive
2600 706 0.67 756 0.86 805 1.04 851 1.20 896 1.36 939 1.52 981 1.67 1023 1.82 1063 1.98 1103 2.13
2800 719 0.78 769 0.96 817 1.14 863 1.31 908 1.47 952 1.62 994 1.78 1035 1.93 1075 2.08 1115 2.24
3000 732 0.89 782 1.08 831 1.25 877 1.42 922 1.58 965 1.74 1007 1.89 1049 2.04 1089 2.19 1128 2.35
3200 747 1.02 797 1.21 846 1.38 892 1.55 937 1.71 980 1.86 1023 2.02 1064 2.17 1104 2.32 1144 2.48
3400 764 1.16 814 1.35 862 1.53 909 1.69 954 1.85 997 2.01 1039 2.16 1080 2.31 1121 2.47 1160 2.62
3600 783 1.33 833 1.51 881 1.69 927 1.86 972 2.02 1016 2.17 1058 2.32 1099 2.48 1139 2.63 1179 2.79
3800 803 1.51 853 1.69 901 1.87 948 2.04 992 2.20 1036 2.35 1078 2.50 1119 2.66 1159 2.81 1199 2.97
4000 825 1.71 875 1.89 923 2.07 970 2.23 1014 2.39 1058 2.55 1100 2.70 1141 2.86 1181 3.01 1221 3.16
4200 849 1.92 899 2.11 947 2.29 993 2.45 1038 2.61 1082 2.77 1124 2.92 1165 3.07 1205 3.23 1245 3.38
4400 874 2.16 924 2.35 972 2.52 1019 2.69 1064 2.85 1107 3.01 1149 3.16 1190 3.31 ----
4600 901 2.42 952 2.61 1000 2.78 1046 2.95 1091 3.11 1134 3.26 1177 3.42 - -----
4800 930 2.70 981 2.88 1029 3.06 1075 3.23 1120 3.39 - - - - - -----
50009612.9910113.1810593.35--------------
3 HP & Field Supplied Drive
ZR150 (12.5 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP & Field Supplied Drive Standard 3 HP & Drive
3200 747 1.02 797 1.21 846 1.38 892 1.55 937 1.71 980 1.86 1023 2.02 1064 2.17 1104 2.32 1144 2.48
3400 764 1.16 814 1.35 862 1.53 909 1.69 954 1.85 997 2.01 1039 2.16 1080 2.31 1121 2.47 1160 2.62
3600 783 1.33 833 1.51 881 1.69 927 1.86 972 2.02 1016 2.17 1058 2.32 1099 2.48 1139 2.63 1179 2.79
3800 803 1.51 853 1.69 901 1.87 948 2.04 992 2.20 1036 2.35 1078 2.50 1119 2.66 1159 2.81 1199 2.97
4000 825 1.71 875 1.89 923 2.07 970 2.23 1014 2.39 1058 2.55 1100 2.70 1141 2.86 1181 3.01 1221 3.16
4200 849 1.92 899 2.11 947 2.29 993 2.45 1038 2.61 1082 2.77 1124 2.92 1165 3.07 1205 3.23 1245 3.38
4400 874 2.16 924 2.35 972 2.52 1019 2.69 1064 2.85 1107 3.01 1149 3.16 1190 3.31 1231 3.47 1270 3.62
4600 901 2.42 952 2.61 1000 2.78 1046 2.95 1091 3.11 1134 3.26 1177 3.42 1218 3.57 1258 3.72 1298 3.88
4800 930 2.70 981 2.88 1029 3.06 1075 3.23 1120 3.39 1163 3.54 1206 3.69 1247 3.85 1287 4.00 1327 4.16
5000 961 2.99 1011 3.18 1059 3.35 1106 3.52 1151 3.68 1194 3.84 1236 3.99 1277 4.14 1318 4.29 1357 4.45
5200 993 3.31 1043 3.49 1092 3.67 1138 3.84 1183 4.00 1226 4.15 1269 4.30 1310 4.46 1350 4.61 1390 4.77
5400 1027 3.64 1077 3.83 1126 4.00 1172 4.17 1217 4.33 1260 4.48 1302 4.64 1344 4.79 1384 4.94 1424 5.10
5600 1063 3.99 1113 4.18 1161 4.35 1207 4.52 1252 4.68 1296 4.84 1338 4.99 1379 5.14 1419 5.29 1459 5.45
5800 1100 4.36 1150 4.55 1198 4.72 1244 4.89 1289 5.05 1333 5.20 1375 5.36 1416 5.51 1456 5.66 - -
6000 1138 4.75 1188 4.93 1237 5.11 1283 5.28 1328 5.44 1371 5.59 1413 5.74 - -----
620011785.1512285.3412775.5113235.68------------
Hi Static 5 HP & Drive 5 HP & Field Supplied Drive

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York PREDATOR R-410A and is the answer not in the manual?

York PREDATOR R-410A Specifications

General IconGeneral
BrandYork
ModelPREDATOR R-410A
CategoryAir Conditioner
LanguageEnglish

Related product manuals