246824-YTG-G-1208
Johnson Controls Unitary Products 65
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZH120 (10 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive Standard 2 HP & Drive Hi Static 3 HP & Drive
2600 675 0.53 726 0.74 776 0.94 824 1.12 870 1.30 914 1.48 957 1.65 1000 1.82 1041 1.99 1082 2.17
2800 686 0.63 738 0.84 787 1.04 835 1.23 881 1.41 925 1.58 969 1.76 1011 1.93 1052 2.10 1093 2.27
3000 699 0.75 750 0.96 800 1.16 847 1.34 893 1.52 938 1.70 981 1.87 1024 2.04 1065 2.21 1106 2.39
3200 713 0.88 764 1.09 814 1.28 861 1.47 907 1.65 952 1.83 995 2.00 1037 2.17 1079 2.34 1119 2.52
3400 728 1.02 779 1.23 829 1.43 877 1.61 923 1.79 967 1.97 1010 2.14 1053 2.31 1094 2.48 1135 2.66
3600 745 1.18 796 1.39 846 1.59 893 1.77 939 1.95 984 2.13 1027 2.30 1069 2.47 1111 2.64 1152 2.82
3800 763 1.36 815 1.57 864 1.76 912 1.95 958 2.13 1002 2.31 1046 2.48 1088 2.65 1129 2.82 1170 3.00
4000 783 1.55 835 1.76 884 1.96 932 2.15 978 2.33 1022 2.50 1066 2.67 1108 2.84 1149 3.02 1190 3.19
4200 805 1.77 856 1.98 906 2.17 953 2.36 999 2.54 1044 2.72 1087 2.89 1129 3.06 1171 3.23 1211 3.41
4400 828 2.00 879 2.21 929 2.41 976 2.59 1022 2.77 1067 2.95 1110 3.12 1152 3.29 ----
4600 852 2.25 904 2.46 953 2.66 1001 2.85 1047 3.03 1092 3.20 1135 3.37 - -----
4800 879 2.52 930 2.73 980 2.93 1027 3.12 1073 3.30 - - - - - -----
50009062.819583.0210073.2210553.41------------
3 HP & Field Supplied Drive
ZH150 (12.5 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP & Field Supplied Drive Standard 3 HP & Drive
3200 713 0.88 764 1.09 814 1.28 861 1.47 907 1.65 952 1.83 995 2.00 1037 2.17 1079 2.34 1119 2.52
3400 728 1.02 779 1.23 829 1.43 877 1.61 923 1.79 967 1.97 1010 2.14 1053 2.31 1094 2.48 1135 2.66
3600 745 1.18 796 1.39 846 1.59 893 1.77 939 1.95 984 2.13 1027 2.30 1069 2.47 1111 2.64 1152 2.82
3800 763 1.36 815 1.57 864 1.76 912 1.95 958 2.13 1002 2.31 1046 2.48 1088 2.65 1129 2.82 1170 3.00
4000 783 1.55 835 1.76 884 1.96 932 2.15 978 2.33 1022 2.50 1066 2.67 1108 2.84 1149 3.02 1190 3.19
4200 805 1.77 856 1.98 906 2.17 953 2.36 999 2.54 1044 2.72 1087 2.89 1129 3.06 1171 3.23 1211 3.41
4400 828 2.00 879 2.21 929 2.41 976 2.59 1022 2.77 1067 2.95 1110 3.12 1152 3.29 1194 3.46 1235 3.64
4600 852 2.25 904 2.46 953 2.66 1001 2.85 1047 3.03 1092 3.20 1135 3.37 1177 3.54 1219 3.72 1259 3.89
4800 879 2.52 930 2.73 980 2.93 1027 3.12 1073 3.30 1118 3.47 1161 3.65 1203 3.82 1245 3.99 1285 4.16
5000 906 2.81 958 3.02 1007 3.22 1055 3.41 1101 3.59 1146 3.76 1189 3.94 1231 4.11 1273 4.28 1313 4.45
5200 936 3.12 987 3.33 1037 3.53 1084 3.72 1130 3.90 1175 4.07 1218 4.24 1260 4.42 1302 4.59 1343 4.76
5400 966 3.45 1018 3.66 1067 3.86 1115 4.05 1161 4.23 1206 4.40 1249 4.57 1291 4.74 1333 4.91 1373 5.09
5600 999 3.80 1050 4.01 1100 4.20 1147 4.39 1193 4.57 1238 4.75 1281 4.92 1323 5.09 1365 5.26 1405 5.44
5800 1032 4.16 1084 4.37 1133 4.57 1181 4.75 1227 4.93 1271 5.11 1315 5.28 1357 5.45 1398 5.62 - -
6000 1067 4.54 1119 4.75 1168 4.95 1216 5.13 1262 5.31 1306 5.49 1350 5.66 - -----
6200 1103 4.94 1155 5.15 1204 5.34 1252 5.53 1298 5.71 - - - - - -----
Hi Static 5 HP & Drive 5 HP & Field Supplied Drive

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York PREDATOR R-410A and is the answer not in the manual?

York PREDATOR R-410A Specifications

General IconGeneral
BrandYork
ModelPREDATOR R-410A
CategoryAir Conditioner
LanguageEnglish

Related product manuals