EasyManuals Logo
Home>York>Air Conditioner>PREDATOR R-410A

York PREDATOR R-410A User Manual

York PREDATOR R-410A
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
246824-YTG-G-1208
80 Johnson Controls Unitary Products
Gas Heat Minimum Supply Air
Size
(Tons)
Model Heat Size
Supply Air (CFM)
Cooling Heating
Min Max Min Max
078
(6.5)
ZH/ZR
10 1950 3250 1950 3250
15 1950 3250 1950 3250
090
(7.5)
ZH/ZR
10 2250 3750 2250 3750
15 2250 3750 2250 3750
102
(8.5)
ZH/ZR
10 2550 4250 2550 4250
15 2550 4250 2550 4250
120
(10)
ZH/ZR
15 3000 5000 3000 5000
20 3000 5000 3000 5000
150
(12.5)
ZH/ZR
15 3750 6250 3750 6250
20 3750 6250 3750 6250
Electric Heat Minimum Supply Air
Size
(Tons)
Model Voltage
Minimum Supply Air (CFM)
Heater kW
9 18243654
078
(6.5)
ZH/ZR/XP
208/230-3-60 1950 1950 1950 1950 -
460-3-60 1950 1950 1950 1950 -
600-3-60 1950 1950 1950 1950 -
090
(7.5)
ZH/ZR/XP
208/230-3-60 2250 2250 2250 2250 -
460-3-60 2250 2250 2250 2250 -
600-3-60 2250 2250 2250 2250 -
102
(8.5)
ZH/ZR/XP
208/230-3-60 2550 2550 2550 2550 -
460-3-60 2550 2550 2550 2550 -
600-3-60 2550 2550 2550 2550 -
120
(10)
ZH/ZR/XP
208/230-3-60 - 3000 3000 3000 3500
460-3-60 - 3000 3000 3000 3000
600-3-60 - 3000 3000 3000 3500
150
(12.5)
ZH/ZR/XP
208/230-3-60 - 3750 3750 3750 4000
460-3-60 - 3750 3750 3750 3750
600-3-60 - 3750 3750 3750 3750
Indoor Blower Specifications
Size
(Tons)
Model
Motor Motor Sheave Blower Sheave
Belt
HP RPM Eff. SF Frame
Datum Dia.
(in.)
Bore (in.) Model
Datum Dia.
(in.)
Bore (in.) Model
078
(6.5)
ZH/ZR/XP
1-1/2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A49
2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 6.0 1 AK64 A49
090
(7.5)
ZH/ZR/XP
1-1/2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A49
3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 5.7 1 AK61 A49
102
(8.5)
ZH/ZR/XP
2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 8.5 1 AK89 A56
3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54
120
(10)
ZH/ZR/XP
2 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 8.0 1 AK84 A56
3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54
150
(12.5)
ZH/ZR/XP
3 1725 0.8 1.15 56 3.4 - 4.4 7/8 1VM50 7.0 1 AK74 A54
5 1725 0.87 1.15 184T 4.3 - 5.3 1-1/8 1VP56 6.7 1 BK77 BX55
Power Exhaust Specifications
Model Voltage
Motor Motor
Fuse Size
CFM @
0.1 ESP
HP RPM
1
1. Motors are multi-tapped and factory wired for high speed.
QTY LRA FLA MCA
2PE04703225 208/230-1-60 3/4 1075 1 7.8 5 6.3 10 3800
2PE04703246 460-1-60 3/4 1075 1 3.4 2.2 2.8 5 3800
2PE04703258 575-1-60 3/4 1050 1 2.9 1.5 1.9 4 3800

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York PREDATOR R-410A and is the answer not in the manual?

York PREDATOR R-410A Specifications

General IconGeneral
BrandYork
ModelPREDATOR R-410A
CategoryAir Conditioner
LanguageEnglish

Related product manuals