Table 34: ZR061 Charging Table
Air Flow
Indoor Db/Wb
Outdoor
DB
Suction
Pressure
Suction
Temp.
Liquid
Pressure
Liquid
Temp.
D el t a T
Db
C o m p r .
amps
300 Cfm/Ton
80/62
75 129 59 279 88 -29 9.7
85 132 59 298 92 -28 10.2
95 136 56 343 102 -27 11.2
300 Cfm/Ton
80/67
75 141 66 279 87 -25 9.7
85 146 63 304 93 -23 10.4
95 150 62 350 102 -22 11.4
300 Cfm/Ton
80/72
75 151 72 278 84 -20 9.6
85 156 71 309 93 -19 10.3
95 162 69 354 102 -18 11.5
300 Cfm/Ton
75/63
75 131 58 279 87 -24 9.8
85 135 58 300 92 -22 10.1
95 140 56 347 100 -21 11.2
400 Cfm/Ton
80/62
75 136 64 279 87 -26 9.7
85 141 65 303 93 -25 10.3
95 145 62 348 102 -24 11.3
400 Cfm/Ton
80/67
75 147 68 279 86 -22 9.6
85 151 68 307 93 -21 10.3
95 156 65 351 102 -19 11.4
400 Cfm/Ton
80/72
75 157 74 279 81 -17 9.5
85 163 74 311 91 -16 10.3
95 169 72 358 102 -15 11.7
400 Cfm/Ton
75/63
75 138 61 279 87 -21 9.7
85 141 60 303 92 -20 10.3
95 145 58 348 100 -18 11.2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York Predator ZR series and is the answer not in the manual?

York Predator ZR series Specifications

General IconGeneral
BrandYork
ModelPredator ZR series
CategoryAir Conditioner
LanguageEnglish

Related product manuals