SECTION 2 – PRODUCT DESCRIPTION
Brazed plate heat exchangers shall be UL (Underwrit-
ers Laboratories) listed. Installing contractor must in-
clude accommodations in the chilled water piping to
allow proper drainage and venting of the heat exchang-
er. Water inlet and outlet connections are grooved for
compatibility with factory supplied victaulic connec-
tions.
The heat exchanger is a brazed plate stainless steel con-
struction, single or dual circuit heat exchanger capable
of refrigerant working pressure of 650 PSIG (3103
kPa) and liquid side pressure of 150 PSIG (1034 kPa)
(Option for 300 PSIG [2068 kPa] available). Each heat
exchanger is covered in 3/4” (19mm) flexible, closed
cell insulation, thermal conductivity of 0.26k (BTU/
HR-FT2 – °F] /in) maximum.
A strainer with a mesh size between .5 and 1.5 mm (40
mesh) is recommended upstream of the heat exchanger
to prevent clogging.
Condenser
Coils – Fin and tube condenser coils of seamless, in-
ternally-enhanced, high-condensing-coefficient, corro-
sion resistant copper tubes are arranged in staggered
rows, mechanically expanded into aluminum fins. Inte-
gral subcooling is included. The design working pres-
sure of the coil is 650 PSIG (45 bar).
Low Sound Fans – The condenser fans are composed
of corrosion resistant aluminum hub and glass-fiber
reinforced composite blades molded into a low noise
airfoil section. They are designed for maximum effi-
ciency and are statically and dynamically balanced for
vibration free operation. They are directly driven by
independent motors, and positioned for vertical air dis-
charge. All blades are statically and dynamically bal-
anced for vibration-free operation. The fan guards are
constructed of heavy-gauge, rust-resistant, PVC coated
steel wire.
Motors – The fan motors are Totally Enclosed Air-
Over (TEAO), direct drive, 6 pole, current protected.
They feature ball bearings that are double-sealed and
permanently lubricated.
CONTROL CENTER
All controls are contained in a NEMA 3R/12 (and
equivalent to IP55*) cabinet with hinged outer door
and includes:
Liquid Crystal Display with Light Emitting Diode
backlighting for outdoor viewing:
Two display lines
Twenty characters per line
Color coded 12-button non-tactile keypad with sec-
tions for:
DISPLAY/PRINT of typical information:
Chilled liquid temperatures
Ambient temperature
System pressures (each circuit)
Operating hours and starts (each compressor)
Print calls up to the liquid crystal display
Operating data for the systems
History of fault shutdown data for up to the last
six fault shutdown conditions.
An RS-232 port, in conjunction with this press-to-
print button, is provided to permit the capability
of hard copy print-outs via a separate printer (by
others).
ENTRY section to:
ENTER setpoints or modify system values.
SETPOINTS updating can be performed to:
Chilled liquid temperature setpoint and range
Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
Low and high ambient cutouts
Number of compressors
Low liquid temperature cutout
Low suction pressure cutout
High discharge pressure cutout
Anti-recycle timer (compressor start cycle time)
Anti-coincident timer (delay compressor starts)
UNIT section to:
Set time
Set unit options

Table of Contents

Other manuals for York YCAL0066

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YCAL0066 and is the answer not in the manual?

York YCAL0066 Specifications

General IconGeneral
BrandYork
ModelYCAL0066
CategoryChiller
LanguageEnglish

Related product manuals