TABLE 1 – MOTOR PROTECTOR DIP SWITCH SETTING
YCAS STYLE F, ACROSS-THE-LINE START – 60 HZ
MODEL VOLT
CHILLER
NO. MOTOR PROTECTOR
NO. CODE
NAMEPLATE
LEADS
MP OL
RLA
PER
VALUE
PHASE
SET
DIP SWITCH SETTINGS ON MP (“1” INDICATES ON)
128 64 32 16 8 4 2 1
0130
17246*21661010 0110
28214*21441001 0000
40130 21751010 1111
46107 11441001 0000
5886 11160111 0100
0140
17267*490 0101 1010
28232*21571001 1101
40140 21891011 1101
46116 11571001 1101
5893 11250111 1110
0150
17295*499 0110 0011
SYS. 1
28256*486 0101 0111
40155 22091101 0001
46128 21731010 1101
58103 11391000 1011
0150
17265*489 0101 1001
SYS. 2
28230*278 0100 1110
40139 21881011 1100
46115 11551001 1011
5892 11240111 1100
0160
17295*499 0110 0011
28256*486 0101 0111
40155 22091101 0001
46128 21731010 1101
58103 11391000 1011
0170
17321*41080110 1100
SYS. 1
28279*494 0101 1110
40169*21140111 0010
46140 21891011 1101
58112 11511001 0111
0170
17295*499 0110 0011
SYS. 2
28256*486 0101 0111
40155 22091101 0001
46128 21731010 1101
58103 11391000 1011
* Indicates one lead/phase through motor protector.