EasyManuals Logo
Home>ABB>Media Converter>ACA 6 Series

ABB ACA 6 Series User Manual

ABB ACA 6 Series
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Chapter 3 Electrical Installation
3-4 ACA 6xx Sections and ACS/ACC 6x7 (132 to 3000 kW) Frequency Converters
Control Cable
Selection
All control cables must be shielded. As a general rule, the control
signal cable shield should be earthed directly in the ACx 600. The other
end of the shield should be left unconnected or earthed indirectly via
some nanofarad high-frequency, high-voltage capacitor (e.g. 3.3 nF /
3000 V). The screen can also be earthed directly at both ends if they
are in the same earth line with no significant voltage drop between the
end points.
Twisting the signal wire with its return wire reduces disturbances
caused by inductive coupling. Pairs should be twisted as close to
terminals as possible.
A double shielded twisted pair cable (Figure a, e.g. JAMAK by NK
Cables, Finland) must be used for analogue signals and the pulse
encoder signals. Employ one individually shielded pair for each signal.
Do not use common return for different analogue signals.
A double shielded cable is the best alternative for low voltage digital
signals but single shielded twisted multipair cable (Figure b) is also
usable.
The analogue and digital signals should be run in separate, screened
cables.
Relay-controlled signals, providing their voltage does not exceed 48 V,
can be run in the same cables as digital input signals. It is
recommended that the relay-controlled signals be run as twisted pairs.
Never mix 24 VDC and 115 / 230 VAC signals in the same cable.
Co-axial Cable Recommendations for use with ACS 600 MultiDrive Application
Controller:
75
W type
RG59 cable with diameter 7 mm or RG11 cable 11
mm
The maximum cable length is 300 m
a
A double shielded twisted
pair cable
b
A single shielded twisted
multipair cable

Table of Contents

Other manuals for ABB ACA 6 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACA 6 Series and is the answer not in the manual?

ABB ACA 6 Series Specifications

General IconGeneral
BrandABB
ModelACA 6 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals