EasyManuals Logo

ABB ACH 500 User Manual

ABB ACH 500
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
Chapter 5 – Standard Application Macro Programs
ACH 500 Programming Manual 5-7
Floating Point Control
External Connections
Connection Example
Figure 5-4 Connection Example
RUN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
REF
GND 2
AI 1+
AI 1-
AI 2+
AI 2-
SPL
GND 2
N.C.
SPL
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
AO 1+
AO 1-
AO 2+
AO 2-
RO 11
RO 12
RO 13
RO 21
RO 22
RO 23
RO 31
RO 32
RO 33
Function
Reference voltage + 10 VDC 10 mA
Auto Reference*
Hand Reference*
Auxiliary voltage output +24 V DC @ 200mA
+24 V max. 10 mA
START HAND
AUTO SELECT
ACCEL
RUN ENABLE
START AUTO
Output Frequency
Output Current
READY
FAULT
A
f
Ready
Run
* Select voltage or current reference with plugs
Fault
120V AC
S1 and S2 on the customer interface board (beside
the screw terminals 1-6 of X50.
DECEL
Terminal X50
1
2
3
4
5
6
+8V Power to remote panel
RS-485 Serial Link Connections
GND2
Shield1
GND3
SGNA
SGNB
7 Shield2
Hand
Reference
Auto
Reference
Terminal X51
Hand
Off
Auto

Table of Contents