34
19
O: Stop
C: Run Fwd
O: Stop
C: Run Rev
Digital input 3
Analog input 1
Preset Speed
O: Selected Speed Ref
C: Preset speed 1 .. 4
Off
Off
Preset Speed 1
On
Off
Preset Speed 2
Off
On
Preset Speed 3
On
On
Preset Speed 4
20
O: Stop
C: Run Fwd
O: Stop
C: Run Rev
Normally Open (N.O.)
Close to increase speed
Normally Open (N.O.)
Close to reduce speed
O: Selected Speed Ref
C: Preset speed 1
21
Normally Open (N.O.)
Close to run Fwd
Normally Closed
(N.C.)
Open to Stop
Normally Open (N.O.)
Close to run Rev
Analog 1 Speed reference
O: Selected Speed Ref
C: Preset speed 1
Note
1) The drive will immediately ramp at the rate set in parameter 2206 2nd DECELERATION RAMP TIME.
2) If a motor thermistor (PTC type only, or normally closed thermal switch contact) is to be connected, this must be selected in
parameter 1304. Connect the thermistor between terminal 1 and terminal 10.
8.2. Macro wiring configurations.
9902 = 1
(Default Macro)
Open
Closed
9902 = 2
Open
Closed
1
+24 Volt Common
1
+24 Volt Common
2
Stop
Run
2
Stop
Run
3
Forward Rotation
Reverse Rotation
3
Forward Rotation
Reverse Rotation
4
Selected Speed ref
Preset Speed ref
4
T4
T6
T10
Preset
5
+10 Volt
5
6
Analog Input 1
6
Open
Open
Open
1202
7
0 Volts
7
Closed
Open
Open
1203
8
8
Open
Closed
Open
1204
9
0 Volts
9
Closed
Closed
Open
1205
10
Preset Speed 1(1202)
Preset Speed 2(1203)
(1203(
10
or
ma
l
Op
er
ati
on
11
11
12
Safe Inhibit
Normal Operation
12
Safe Inhibit
Normal Operation
13
Safe Inhibit
Normal Operation
13
Safe Inhibit
Normal Operation
9902 = 3
Open
Closed
9902 = 4
Open
Closed
1
+24 Volt Common
1
+24 Volt Common
2
Stop
Run
2
Stop
Run
3
Forward Rotation
Reverse Rotation
3
Forward Rotation
Reverse Rotation
4
Selected Speed ref
Preset Speed 1 (1202)
4
Selected Speed ref
Preset Speed 1 (1202)
5
+10 Volt
5
+10 Volt
6
Analog Input 1
6
Analog Input 1
7
0 Volts
7
0 Volts
8
8
9
0 Volts
9
10
Analog input 2 (E.g. Torque Reference)
10
or
m
al
O
pe
ra
ti
on
Decel ramp 1 (2203)
Decel ramp 2 (2206)
1)
11
11
12
Safe Inhibit
Normal Operation
12
Safe Inhibit
Normal Operation
13
Safe Inhibit
Normal Operation
13
Safe Inhibit
Normal Operation
Note
1) The drive will immediately ramp at the rate set in parameter 2206 2nd DECELERATION RAMP TIME.
9902
Digital Input 1
(Terminal 2)
Digital Input 2
(Terminal 3)
Digital Input 3
(Terminal 4)
Analog Input 1
(Terminal 6)
Analog Input 2
(Terminal 10)

Table of Contents

Other manuals for ABB ACS255

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS255 and is the answer not in the manual?

ABB ACS255 Specifications

General IconGeneral
BrandABB
ModelACS255
CategoryController
LanguageEnglish

Related product manuals