Installation
46
Requirements for the installation site
The drive must be installed in an upright position on floor (or wall). Check the
installation site according to the requirements below. Refer to Dimensional drawings
for frame details. See Technical data for the allowed operation conditions of the
drive.
Wall
The wall/material near the unit must be of non-flammable material. Check that there
is nothing on the wall to inhibit the installation.
If a unit is mounted on the wall, the wall must be as close to vertical as possible, and
strong enough to carry the weight of the unit. The drive must not be installed without
the pedestal and a support shelf on wall, refer to ACS800-02/U2 Application Note on
Wall Mounting [68250013 (English)].
Floor
The floor/material below the installation should be non-flammable. The floor must be
horizontal.
Free space around the unit
See section Installation procedure: Choose the mounting orientation (a, b, c or d).
Cooling air flow
Provide the drive with the amount of fresh cooling air given in Technical data / IEC
ratings or US tables.
The cooling air will enter the unit from the front air grating and flow upwards inside
the unit. Recirculating cooling air into the unit is not allowed.