EasyManuals Logo
Home>ABB>Control Systems>ACS800-02

ABB ACS800-02 User Manual

ABB ACS800-02
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
Safety instructions
6
Installation and maintenance work
These warnings are intended for all who work on the drive, motor cable or motor.
Ignoring the instructions can cause physical injury or death.
Only qualified electricians are allowed to install and maintain the drive.
Never work on the drive, the motor cable or the motor when main power is
applied. After switching off the input power, always wait for 5 min to let the
intermediate circuit capacitors discharge before you start working on the drive,
the motor or the motor cable.
Always ensure by measuring with a multimeter (impedance at least 1 Mohm)
that:
1. Voltage between drive input phases U1, V1 and W1 and the frame is close to
0V.
2. Voltage between terminals UDC+ and UDC- and the frame is close to 0 V.
Do not work on the control cables when power is applied to the drive or to the
external control circuits. Externally supplied control circuits may cause
dangerous voltages inside the drive even when the main power on the drive is
switched off.
Do not make any insulation or voltage withstand tests on the drive or drive
modules.
When reconnecting the motor cable, always check that the phase order is
correct.
Note:
The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
The brake control terminals (UDC+, UDC-, R+ and R- terminals) carry a
dangerous DC voltage (over 500 V).
Depending on the external wiring, dangerous voltages (115 V, 220 V or 230 V)
may be present on the terminals of relay outputs RO1 to RO3.
ACS800-04: the busbar ends on both sides of the pedestal are at a
dangerously high voltage when the input power is on, regardless of whether the
motor is running or not.
ACS800-02 with enclosure extension: The main switch on the cabinet door
does not remove the voltage from the input busbars of the drive. Before working
on the drive, isolate the whole drive from the supply.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS800-02 and is the answer not in the manual?

ABB ACS800-02 Specifications

General IconGeneral
BrandABB
ModelACS800-02
CategoryControl Systems
LanguageEnglish

Related product manuals