30 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971)
Description
General
This protection function monitors the temperature of a motor with Pt100 sensors in a
potentially explosive atmosphere. It is possible to
monitor the motors stator (+3L514+Q971)
monitor bearings and stator (+5L514+Q971) or
monitor the bearings and double-monitor the stator (+8L514+Q971).
The function is activated when the motor temperature exceeds the set operating
temperature limit of the Pt100 relay. The function activates the Safe torque off (STO)
function of the drive. This disables the control voltage of the power semiconductors of the
drive output stage. This prevents the inverter from generating the torque required to rotate
the motor. The motor coasts to a stop.
ACS880-07/17/37 drives with the option +Q978:
Also the main contactor/breaker is
opened.
ACS880-07 drives, frames nxDXT + nxR8i with a main contactor/breaker (option +F250/
+F255) and ACS880-17/37 drives, frames nxR8i + nxR8i: When the STO function is
activated in the inverter unit, the main contactor/breaker is opened after user-defined delay
(defined with parameter 94.11, the default value is 600 s). See hardware and firmware
manuals for more information.
Other safety functions in the drive can also use the STO function. In addition, an FSO
module can be included in the activation sequence of the ATEX-certified motor thermal
protection function. See the circuit diagrams delivered with the drive for the actual safety
circuitry.
The FSO safety functions module (FSO-12 or FSO-21) is an optional device used with the
ACS880 drives to implement safety functions. When installed, it reserves the standard
STO connection of the drive. In this case, the FSO module activates the STO function of
the drive (that is, opens the drive STO circuit) either immediately or after a deceleration
ramp.
You can implement the motor thermal protection function with or without an FSO safety
functions module:
Without an FSO module, the opening contacts of the Pt100 relay(s) open the STO
circuit of the drive (see section Without an FSO module on page 32).
With an FSO module, the opening contacts of the Pt100 relay(s) activate the STO or
Safe stop 1 (SS1) function of the FSO module and the FSO module opens the STO
circuit of the drive (see section With an FSO module on page 33). For more
information on the safety functions of the FSO module, see FSO-12 safety functions
module users manual (3AXD50000015612 [English]) or FSO-21 safety functions
module users manual (3AXD50000015614 [English]).
Always consider which stop category (0 = immediate STO or 1 = delayed STO after SS1)
is more appropriate for the motor in overtemperature situations.
The protection function circuit is motor specific, also in multidrives where several motors
are connected. The function stops only the motor where overtemperature is detected.
It is possible to get information on the status of the protection function by means of a
normally-open contact. The information can be obtained separately from the bearing and
stator sensors. The contact can be wired to a digital input on the drive control unit or to an
external control system. For instructions, see section Wiring on page 37.
00 ACS880 ATEX cabinet.book Page 30 Tuesday, May 28, 2019 10:25 AM

Table of Contents

Other manuals for ABB ACS880-17

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880-17 and is the answer not in the manual?

ABB ACS880-17 Specifications

General IconGeneral
BrandABB
ModelACS880-17
CategoryDC Drives
LanguageEnglish

Related product manuals