5 CONTROL OPERATION
…5.10.1 Control Page (Heat/Cool Control)
Manual Reset (cool output)
Set the required proportional band offset, between 0.0 and 100.0% of the
engineering range span in 0.1% increments.
Derivative Action Time
Set the required time between 0.1 and 999.9 in 0.1 second increments (999.9
seconds = 16.67 minutes). '
OFF' is selected below 0.1.
Approach Band
Set the required value between 0.1 and 3.0 in 0.1 increments. (Set 1.0 initially).
Crossover Output Value
Set the required value between 0.0 and 100.0% of the PID output, in 0.1%
increments – see Section 5.10.2.
Transition Bandwidth
Set the required value between 0.0 and 100.0% of the PID output, in 0.1%
increments – see Section 5.10.3.
Output Off Hysteresis Band
Set the required value which prevents oscillation of control changes, between 0.0 and
25.0% of the PID output, in 0.1% increments.
5.10.2 Calculating the Crossover Value – Fig. 5.18
The crossover value is calculated from the expression:
100
Gh/Gc + 1
Crossover Value =
Where Gh/Gc is the ratio of the two output driver gains.
The most common method for determining the Gh/Gc term is by
using 'nameplate' values from the heat/cool device(s).
If a heat/cool application can produce a maximum of 1.5kW and
absorb 0.75kW:
1.5
0.75
Output Gain Ratio = = 2
100
2 + 1
Crossover Value = = 33.3%
5.10.3 Calculating the Transition
Bandwidth Value – Fig 5.18
The Transition Bandwidth is the percentage difference of the
proportional band settings.
Example – if the proportional band settings for the heat output is
20% and for the cool output is 25%:
25 – 20
25
x 100
Transition Bandwidth (%) =
Transition Bandwidth = 20%
If the proportional band settings for both outputs are equal, the
bandwidth is 0%. As a general rule, the Transition Bandwidth
should not exceed 30%.

Other manuals for ABB C1900 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB C1900 Series and is the answer not in the manual?

ABB C1900 Series Specifications

General IconGeneral
BrandABB
ModelC1900 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals