EasyManuals Logo
Home>ABB>Adapter>FPBA-01 PROFIBUS DP

ABB FPBA-01 PROFIBUS DP User Manual

ABB FPBA-01 PROFIBUS DP
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #155 background imageLoading...
Page #155 background image
Communication protocol 155
The table below lists the error codes for the DP-V1 error
responses.
Error class Meaning Error code
0…9 (Reserved)
10 (0x0A) Application 0 = Read error
1 = Write error
2 = Module failure
3…7 = Reserved
8 = Version conflict
9 = Feature not supported
10…15 = User-specific
11 (0x0B) Access 0 = Invalid index
1 = Write length error
2 = Invalid slot
3 = Type conflict
4 = Invalid area
5 = State conflict
6 = Access denied
7 = Invalid range
8 = Invalid parameter
9 = Invalid type
10…15 = User-specific
12 (0x0C) Resource 0 = Read constraint conflict
1 = Write constraint conflict
2 = Resource busy
3 = Resource unavailable
4…7 = Reserved
8…15 = User-specific
13…15 User-specific
xxxxxxxx
MSB LSB

Table of Contents