Start-up 59
Starting up ACSM1 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter 50.01 FBA ENABLE to Enable.
3. With parameter 50.02 COMM LOSS FUNC, select how the
drive reacts to a fieldbus communication break.
Note that this function monitors both communication between
the fieldbus master and the adapter module and
communication between the adapter module and the drive.
4. With parameter 50.03 COMM LOSS T OUT, define the time
between communication break detection and the selected
action.
5. Select application-specific values for parameters
50.0450.11. Examples of appropriate values are shown in
the tables below.
6. Set the FPBA-01 configuration parameters in group 51. At the
minimum, set the required node address in parameter 51.02
and the communication profile in 51.05.
7. Define the process data transferred to and from the drive in the
FPBA-01 configuration parameter groups 52 and 53.
Note: The adapter module sets the Status word and Control
word automatically in parameters 52.01 and 53.01.
8. Validate the settings made in parameter groups 51, 52 and 53
by setting parameter 51.27 FBA PAR REFRESH to
REFRESH.
9. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB FPBA-01 PROFIBUS DP and is the answer not in the manual?

ABB FPBA-01 PROFIBUS DP Specifications

General IconGeneral
BrandABB
ModelFPBA-01 PROFIBUS DP
CategoryAdapter
LanguageEnglish

Related product manuals