1MRS750527-MUM
)HHGHU7HUPLQDO
Technical Reference Manual, General
5()B
71
)LJ 0HQXOHYHOVWUXFWXUH
For more detailed information about the HMI, please refer to the Operator’s Manual
(1MRS 750500-MUM).
$ODUP/('LQGLFDWRUV
The REF 54_ feeder terminal offers eight alarm LED indicators to be configured
with the Relay Mimic Editor. The LED colors are green, yellow or red, and their use
can be freely defined (for defining the ON and OFF state texts, refer to section
“MIMIC configuration” on page 24). Three basic operation modes are supported:
• non-latched light
• latched-steady light
• latched blinking light
Alarms can be acknowledged remotely, locally or by using logic.
The alarm channels include time tagging for detected alarms. The time tagging
principle used depends on the operation mode.
The alarm channels are seen as function blocks in the feeder terminal configuration:
21 kV
CB OK
menupict
E
E
Setting group 1
MEASUREMENT
EVENT view
ALARM view
USER LEVEL (LEVEL 1)
TECHNICAL LEVEL (LEVEL 2)
MIMIC view
MEASUREMENT view
EV ENTS
IL1-A 00250.0
IL2-A 00252.0
IL3-A 00249.0
Io-A 00000.0
Iob-A 00000.0
Uo-V 000000
U1-kV 020.00
U2-kV 020.00
U3-kV 020.00
f-Hz 50.00
Demand values
IL1-A 00248.0
IL2-A 00251.0
IL3-A 00250.0
Power
P-kW 006928
NOC3Low 31/E1
1999-12-24
18:35:12.230
NOC3Low 31/E1
1999-12-24
18:35:12.330
NOC3High 32/E1
1999-12-24
14:25:52.720
NOC3High 32/E3
1999-12-24
14:25:52.760
Event list
MEAS ALARM
CB spring ready
SF6 gas density
Temperature
Interlocking
PARAMETER MENU
GROUP MENU
MAIN MENU
MAIN MENU
2 Sec
1 Sec
Protection
NOC3Low
SUBGROUP MENU
Operation mode
= Definite time
Start current
=3.1 x In
Operate time
= 041.03 s
Time multiplier
= 0.78
C clears ALARMs
EVENT MIMIC
Updating values
MIMIC EVENT
Actual setting
Setting group 1
Setting group 2
Control setting
Input data
Output data
Recorded data 1
Recorded data 2
Recorded data 3
Status
Protection
Control
Cond. monit.
Measurement
Communication
General func.
Tests
Information
Configuration
CUB3Low
DEF2Low
DEF2High
DEF2Inst
Freq1
Freq2
Freq3
Freq4
Freq5
Inrush3
NEF1Low
NEF1High
NEF1Inst
NOC3Low
NOC3High
NOC3Inst
MIMIC view
ALARM MEAS
E MIMIC Submenu
, Move cursor
, Move cursor
MainMenu Next
, Move cursor
Prev. Param.
, Move cursor
Prev. E Set
$ODUPFKDQQHO )XQFWLRQEORFN
Alarm channel 1 MMIALARM1
Alarm channel 2 MMIALARM2
Alarm channel 3 MMIALARM3