Specifications
42/18-84-EN TZIDC, TZIDC-110, TZIDC-120 43
9.1.10 Accessories
Mounting material
- Attachment kit for linear actuators to DIN/IEC 534 / NAMUR
- Attachment kit for rotary actuators to VDI / VDE 3845
- Attachment kit for integral mounting to control valves
- Attachment kit for actuator-specific attachment upon request
Pressure gauge block
- With pressure gauges for supply and output pressure.
- Pressure gauges with housing ø 28 mm
- Aluminum connection block in black
- Installation material in black for mounting to TZIDC
Filter regulator
All metal version in brass, varnished black, bronze filter element,
(40 µm) , with condensate drain.
max. pre-pressure 16 bar (232 psi), output adjustable to 1.4 ... 6 bar
(20.31 ... 90 psi).
IMPORTANT (NOTE)
The filter regulator may only be installed in combination with
the pressure gauge block (accessory).
PC adapter for communication
LKS adapter for plug-in connection to TZIDC
FSK modem for HART communication
PC software for remote configuration and operation
DSV401 (SMART VISION) with DTM for TZIDC to CD-ROM
9.2 TZIDC-110
9.2.1 Communication
Profiles Profibus PA profile for process
devices
Electro-pneumatic actuators V3.0
Block types 1 AO Functional block
1 Transducer block
1 physical block
Physical Layer
In compliance with IEC 61158-2
Transmission rate
31.25 Kbit/s
Supply voltage
Power feed from the PA bus,
9.0 ... 32.0 V DC
Max. permissible voltage
35 V DC
Power consumption
10.5 mA
Current in the event of an
error
15 mA (10.5 mA + 4.5 mA)
9.2.2 Device name
Device name TZIDC-X10
PNO ID no. 0x0639
Dev. ID 0X3200028xyz
Bus address Between 0 and 126, default address
126
9.2.3 Output
Range 0 ... 6 bar (0 ... 90 psi)
Air capacity at 1.4 bar (20 psi) supply pressure
5.0 kg/h = 3.9 Nm
3
/h = 2.3 scfm
at supply pressure of 6 bar (90 psi)
13 kg/h = 10 Nm
3
/h = 6.0 scfm
Output function For single or double-acting actuators,
air is vented from actuator or actuator
is blocked in case of (electrical) power
failure
Shut-off values end position 0 % = 0 ... 45 %
end position 100 % = 55 ... 100 %
9.2.4 Travel
Ste
Rotation angle
Used range
25 … 120° rotary actuators, optionally 270°
25 … 60° linear actuators
Travel time
prolongation
Setting range 0 ... 200 seconds, separately for each
direction
9.2.5 Air supply
Instrument air free of oil, water and dust to DIN/ISO
8573-1. Pollution and oil content
according to Class 3 (purity: max.
particle size = 5 µm, max. particle density
= 5 mg / m
3
; oil content: max.
concentration = 1 mg / m
3
; pressure dew
point: 10 K below operating temperature)
Supply pressure 1.4 ... 6 bar (20 ... 90 psi)
IMPORTANT (NOTE)
Do not exceed the maximum operating pressure of the
actuator!
Air consumption < 0.03 kg/h / 0.015 scfm (independent
of supply pressure)