Ex relevant specifications
48 TZIDC, TZIDC-110, TZIDC-120 42/18-84-EN
Change from one to two colu mns
10 Ex relevant specifications
IMPORTANT (NOTE)
The values indicated here are taken from the respective certificates. Always observe the
specifications and supplements in the explosion protection certificates.
10.1 TZIDC
s
10.1.1 ATEX
ATEX II 2G Ex ia IIC T6
II 2G Ex ib IIC T6
2 II D IP6x T 46°C
Type-Examination Test Certificate: TÜV 04 ATEX 2702 X
Type: Intrinsically safe equipment
Device class: II 2G (Ex ia IIC)
II 2G (Ex ib IIC)
Standards: EN 60079-0:2006
EN 60079-11:2007
EN 61241-0:2006
EN 61241-11:2006
Temperature class Ambient temperature range (II 2 G)
T4 -40 ... 85 °C
T5 -40 ... 50 °C
T6
1)
-40 ... 40 °C
1) When using the plug-in module for "Digital Feedback" in Temperature Class T6, the maximum permissible ambient
temperature range is -40 … 35 °C.
Housing surface temperature Ambient temperature range (II 2 D)
T81 °C -40 ... 70 °C
T61 °C -40 ... 50 °C
T51 °C -40 ... 40 °C