Ex relevant specifications
42/18-84-EN TZIDC, TZIDC-110, TZIDC-120 53
When installed per installation Drawing No 901064
Temperature Code T4
Max. Ambient 85 Deg C
IMPORTANT (NOTE)
• The "x" in P/N denotes minor mechanical variations or optional features.
• Do not use the local communication interface (LKS) in hazardous areas.
• Each pair of conductors for each intrinsic safety circuit must be shielded.