Universal Serial Bus (USB) to DH-485 Interface Converter 13
Publication 1747-IN063C-EN-P - January 2006
8. The 1747-UIC interface converter operates at 19.2 Kbps only, so set the Baud
Rate to 19200.
Do not click AutoConfigure.
9. Assign the 1747-UIC interface converter an unused station number on the
DH-485 network to which you are connecting.
The interface converter cannot go online to a DH-485 network if it’s
assigned station number is already being used. Station number 0 is typically
reserved for use by RSLinx, but any station number from 0 to 31 is valid.
10. Click OK.
The 1747-UIC interface converter appears on the network at node 0, as
shown in the example below.
Uninstall the Drivers
To uninstall the 1747-UIC drivers from a computer:
1. Choose Add/Remove Programs from the Windows Control Panel.
2. Select FTDI USB Serial Converter Drivers.
IMPORTANT
Always stop the RSLinx RS-232 DF1 driver or shut down
RSLinx prior to unplugging the interface converter from the
computer’s USB port.