Rockwell Automation Publication 842E-UM001C-EN-P - September 2016 59
Configuring the 842 E Encoder Using RSLogix 5000® Chapter 6
Configuration Tab
Figure 15
The Configuration tab is used to configure the encoder scaling, direction, and
set velocity units. Click the Enable Scaling checkbox to change the encoder
resolution. Use the Direction drop down box to set the direction of the
encoder (check the definition in the old user manual). Use the velocity units to
set the velocity units of the encoder.
Scaling makes it possible to scale the steps per revolution and the total
resolution (see Linear Scaling Example on page 75
in Appendix B).
If the Enable Scaling box is checked, the values can be entered for the steps per
revolution and the total resolution applied.
Direction: The direction of rotation (increase position value), viewed on the
shaft, can be set to clockwise or counterclockwise.
Clockwise = increase position value on clockwise revolution of the shaft
Counterclockwise = increase position value on counterclockwise
revolution of the shaft.
Vel o c it y units : Use this parameter to define the units in which the velocity is
transmitted. The options are the following:
Counts/sec
Revolutions/sec
Revolutions/min

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley EtherNet/IP 842E-SIP1BA and is the answer not in the manual?

Allen-Bradley EtherNet/IP 842E-SIP1BA Specifications

General IconGeneral
BrandAllen-Bradley
ModelEtherNet/IP 842E-SIP1BA
CategoryMedia Converter
LanguageEnglish

Related product manuals