PowerFlex 700 Technical Data
46 20B-TD001F-EN-P
Mounting
Operating Temperatures
PowerFlex 700 drives are designed to operate at 0° to 40° C ambient. To operate the drive in installations between 41° and
50° C, see the information below and refer to pages 33-39 for exceptions.
Acceptable Surrounding Air Temperature & Required Actions
Minimum Mounting Clearances
Frames 0…6
Specified vertical clearance requirements are intended to be from drive to drive. Other objects can occupy this space;
however, reduced airflow may cause protection circuits to fault the drive. In addition, inlet air temperature must not
exceed the product specification.
Frames 7…10
The drive must be mounted with sufficient space at the top, sides, and front of the cabinet to allow for proper heat
dissipation.
Enclosure Rating Temperature Range Drive
IP20, NEMA/UL Type 1 (with Top Label)
(1)
(1)
Removing the adhesive top label from the drive changes the NEMA/UL enclosure rating from Type 1 to Open. Frames 5 and 6 do not have a top label.
0…40° C Frames 0…4, All Ratings
0…50° C Frames 5…6, Most Ratings
(2)
(2)
Refer to pages 33-37 for exceptions.
IP20, NEMA/UL Type Open (Top Label Removed)
(1)
0…50° C Most Ratings
(2)
0…45° C 20BC072 Only
IP00, NEMA/UL Type Open (Top Label & Vent Plate Removed) 0…50° C 20BC072 Only
(3)
(3)
To remove vent plate (see page 51 for location), lift top edge of plate from the chassis. Rotate the plate out from the back plate.
Flange Mount
Front - IP00, NEMA/UL Type Open
Back/Heat Sink - IP54, NEMA/UL Type 12
0…40° C Back (External)
0…55° C Front (Inside Enclosure)
Frames 5…6
Stand-alone/Wall Mount - IP54, NEMA/UL Type 12 0…40° CFrames 5…6
Frame Recommendations
7 Allow a minimum of 152 mm (6.0 in.) at the top and bottom of the enclosure and 102 mm (4.0 in.) on the
sides.
Flange Mount - Allow a minimum of 152 mm (6.0 in.) at the back of the enclosure (from flange mount
surface to wall).
8…10 Allow a minimum of 152 mm (6.0 in.) at the top of the enclosure. Additionally, allow a minimum of 102 mm
(4.0 in.) on each side OR 152 mm (6.0 in.) in the back.
101.6 mm
(4.0 in.)
101.6 mm
(4.0 in.)
50.8 mm
(2.0 in.)
101.6 mm
(4.0 in.)
101.6 mm
(4.0 in.)
PWR
STS
PORT
MOD
NET A
NET B
PWR
STS
PORT
MOD
NET A
NET B
No Adhesive Label
(see table above)
With Adhesive Label
(see table above)
101.6 mm
(4.0 in.)
101.6 mm
(4.0 in.)
101.6 mm
(4.0 in.)
101.6 mm
(4.0 in.)
PWR
STS
PORT
MOD
NET A
NET B
PWR
STS
PORT
MOD
NET A