Installation Procedure
Autopulse-442R 50098:F 05/24/2001 25
2XWSXW6XSHUYLVRU\5HOHDVLQJ6HUYLFH
Set the function of Output 4 via SW1 DIP switch 2.
5HOHDVLQJ&LUFXLW'HOD\7LPHU
Select the desired Timer setting and set SW1 DIP switches 3 and 4 per the appropriate column.
$ERUW)XQFWLRQ
Select the desired abort functions for delaying the activation of releasing circuits, and set SW1 DIP
switches 5 and 6 per the appropriate column. If Cross-zone is selected, both Zone 1 and Zone 2
must be activated to start timer.
Switch #2 OFF Switch #2 ON
Output 4
will function as a solenoid releasing
circuit. This circuit will be a non-power limited
circuit in this mode.
Output 4
will function as a supervisory input circuit.
A short condition on this circuit will light the
Supervisory LED and sound the supervisory tone on
the piezo. An open condition generates a circuit
trouble condition. This circuit will function as a
power limited circuit in this mode.
No Delay* 10-Second Delay 20-Second Delay 30-Second Delay
Switch 3 OFF,
Switch #4 OFF
Switch 3 OFF,
Switch #4 ON
Switch 3 ON,
Switch #4 OFF
Switch 3 ON,
Switch #4 ON
*ABORT timer will not operate when timer is set for “NO DELAY”.
Standard “Deadman”
UL-type Delay Timer*
Switch #5 OFF,
Switch #6 OFF
IRI-type
Delay Timer*
Switch #5 OFF,
Switch #6 ON
NYC-type
Delay Timer
Switch #5 ON,
Switch #6 OFF
Local Jurisdiction
Delay Timer
Switch #5 ON,
Switch #6 ON
Continues to count down
upon ABORT, but stops
and holds at 10 seconds
until release of the
ABORT switch. Upon
release of the ABORT
switch, the timer
resumes the countdown
at 10 seconds.
Functions the same as
the UL-type timer with
the exception that the
ABORT will function
only if pressed and held
before 2nd zone goes
into alarm.
When an alarm exists,
pressing ABORT
changes timer value to
the Timer Delay plus 90
seconds. The timer will
not start while ABORT
is held. SYSTEM
RESET restores timer to
original Timer Delay.
Each time ABORT is
pressed again adds 90
seconds to Timer Delay.
Once the timer has
started, pressing ABORT
resets the timer to full
Timer Delay. The timer
will not start while
ABORT is held.
Releasing the ABORT
switch continues the
countdown; pressing
ABORT again restores
Timer Delay to its full
value.
Note: ABORT timer will not operate when timer is set for “NO DELAY”. Manual pull station does not use
abort mode.