Rigging
Refer to Table 1 and Figures 1 and 2 for the required minimum spreader bar and the
recommended vertical dimension “H” from the lifting device at the base of each unit or
section to the spreader bar. Figure 1 shows the proper rigging of a Series 1500 that ships
in one-section. Figure 2 shows the proper rigging of a two-section unit.
Figure 1. Single Piece Lift
Table 1. Minimum Vertical Dimension and Spreader Bar Length
2
NOTE: Models S15E/XES15E-x-06x
and S15E/XES15E-x-07x ship in a
single piece. All other models ship
in two sections per cell.
Figure 2. Two-Section Cells
Model Number
Min.
W1
(ft)
Single Piece Lower Section Upper Section
Min. H (ft) Min. W2 (ft) Min. H (ft) Min. W2 (ft) Min. H (ft) Min. W2 (ft)
S15E/XES15E-1285-06x 12 11 6 — — — —
S15E/XES15E-1285-07x 12 12 6 — — — —
S15E/XES15E-1285-09x 12 15 6 7 5.5 9 6
S15E/XES15E-1285-10x 12 16 6 8 5.5 9 6
S15E/XES15E-1212-07x 12 12 6 — — — —
S15E/XES15E-1212-09x 12 15 6 7 5.5 9 6
S15E/XES15E-1212-10x 12 16 6 8 5.5 9 6
S15E/XES15E-1212-11x 12 17 6 9 5.5 9 6
S15E/XES15E-1212-12x 12 19 6 11 5.5 9 6
S15E/XES15E-1218-07x 12 12 6 — — — —
S15E/XES15E-1218-09x 12 15 6 7 5.5 9 6
S15E/XES15E-1218-10x 12 17 6 9 5.5 9 6
S15E/XES15E-1218-11x 12 18 6 10 5.5 9 6
S15E/XES15E-1218-12x 12 19 6 11 5.5 9 6
WARNING: Failure to use lifting
provisions can result in a dropped
load causing severe injury, death,
and/or property damage. Lifts
must be performed by qualified
riggers following BAC published
Rigging Instructions, and generally
accepted lifting practices. The
use of a supplemental safety
sling may also be required if the
lift circumstances warrant its
use, as determined by the rigging
contractor.
Upper Section
Lower Section
1/2”
Flat