Product overview
BK3xx012 Version: 4.3.0
Technical data BK3150
Type BK3150
Number of Bus Terminals 64 (255 with K-bus extension)
Digital peripheral signals 256 inputs/outputs (BK3x10)
Analog peripheral signals 128 inputs/outputs (BK3x00)
Configuration possibility Via the KS2000 configuration software or the
controller
Max. number of bytes
(inputs and outputs)
128 bytes (DP operation only)
Baud rate (automatic detection) up to max. 12 Mbaud
Bus connection 1 x D-sub plug, 9-pin with shielding
Power supply (Us) 24V
DC
(-15% /+20%) Use a 4A fuse or an NEC
Class2 power supply to meet the UL requirements!
Input current (Us) 70 mA + (total K bus current)/4, max. 320 mA
Starting current (Us) 2.5 x continuous current
K-bus current (5 V) up to hardware version 04: 1000mA
from hardware version 05: 1750mA
Power contact voltage (Up) maximum 24V
DC
Power contacts current load (Up) maximum 10A
Recommended backup fuse (Up) maximum 10A
Electrical isolation Power contact / supply / fieldbus
Dielectric strength 500V (power contact/ supply/ fieldbus)
Weight approx. 100 g
Permissible ambient temperature (operation) -25°C … +60°C
Permissible ambient temperature (storage) -25°C … +85°C
Permissible relative humidity 95% (no condensation)
Vibration/shock resistance conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission conforms to EN 61000-6-2 / EN 61000-6-4
Protection class IP20
Installation position variable
Approvals
CE, ATEX [}33], cULus