EasyManuals Logo
Home>Beckhoff>Adapter>BK3120

Beckhoff BK3120 User Manual

Beckhoff BK3120
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
PROFIBUS DP communication
BK3xx056 Version: 4.3.0
Byte Bit Value Description
3 5 1
bin
Dummy output byte
activated
It is also necessary for the dummy output byte to be configured in the CfgData before the complex terminals:
CfgData DP modules
0x20 Dummy output byte
K-bus cycle counter
In order for the master to be able to check reliably whether precisely one (or two) K-bus cycles are always
being carried out during one DP cycle, a K-bus cycle counter can be transferred in the input data from the
Bus Coupler to the master. This is incremented after each K-bus cycle (0 is omitted, so that 1 follows after
255). The K-bus cycle counter must be activated in the UserPrmData and entered as a module in the
CfgData. The extended GSD file for the Bus Coupler is, however, necessary for this:
Byte Bit Value Description
3 3 1
bin
K-bus cycle counter
activated
It is also necessary for the K-bus cycle counter byte to be configured in the CfgData before the complex
terminals:
CfgData DP modules
0x10 K-bus cycle counter
5.2 DPV1 - acyclic data transfer
5.2.1 DPV1 Interface
By default, one MSAC_C1 connection and one MSAC_C2 connection with 52 bytes of data (4 bytes DPV1
header plus 48 bytes of user data) are supported. The MSAC_C1 connection is established along with cyclic
connection, and can be activated via the UserPrmData [}35]:
Byte Bit Value: Description
0 7 1: MSAC_C1 connection is activated
The MSAC_C2 connection can be used either by the C1 master (which communicates with the slave
cyclically) or by a C2 master (which then only communicates with the slave acyclically), and has its own
establishment of connection. The parameters at the establishment of the MSAC_C2 connection
(Feature_Supported, Profile_Feature_Supported, Profile_Ident_Number, etc.) are not examined, and the
parameters of the request are mirrored in the response.
Slot_Number [}57] = 0 addresses PROFIBUS coupler data, Slot_Number [}57] > 0 addresses the data of
the function module(s).