Parameterization and commissioning
BK3xx042 Version: 4.3.0
Note regarding GSD file
The GSD file contains a maximum of 244 bytes of input, output and configuration data. These are
the maximum values. Below are the default of values and the setting options.
DP buffer Default Maximum size
Inputs 128 244
Outputs 128 244
Diagnostic Data 64 64
Configuration data 64 244
The sizes can be adjusted through the PrmData [}73]. The length is changed in 8-byte steps.
Sample
If it is desired to increase the size of the input data, other sizes must be reduced to compensate.
If we have 20 x 4 channel KL3314 thermocouples, then in compact mapping we find 20 Bus Terminals * 4
channels * 2 bytes per channel = 20 * 4 * 2 = 160 bytes
160 bytes is larger than the 128 byte default figure - settings must therefore be modified.
Set PrmData byte 12 bits 4-7 to 15
dec
or 0xF
hex
, set byte for 37 to 160 (input data) and byte 38 to 96 (output
data).
4.4.6 KS2000 - Introduction
The KS2000 configuration software permits configuration, commissioning and parameterization of bus
couplers, of the affiliated bus terminals and of Fieldbus Box Modules. The connection between bus coupler/
Fieldbus Box Module and the PC is established by means of the serial configuration cable or the fieldbus.
Fig.24: KS2000 configuration software

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff BK3120 and is the answer not in the manual?

Beckhoff BK3120 Specifications

General IconGeneral
BrandBeckhoff
ModelBK3120
CategoryAdapter
LanguageEnglish

Related product manuals