14 | UPM SequenCE of Operation EP Series
EP Series
8733953041 (2019/01)
Subject to change without prior notice
UPM SEQUENCE OF OPERATION
Figure # 17 UPM Sequence of Operation
LEGEND:
HPC - HIGH PRESSURE CUTOUT
LPC - LOW PRESSURE CUTOUT
FRZ - FREEZE PROTECTION CONDITION
CON - CONDENSATE OVERFLOW CONDITION
CC - COMPRESSOR COIL
ASC - ANTI SHORT CYCLE
CC
LOCKOUT CAN BE SET
TO 4 VIA DIP SWITCH
BLINK CODE ON STATUS LED
SOFT LOCKOUT
RECORD ALARM
START COUNTER (IF APPLICABLE)
CC OUTPUT = ON
NO
YES
LPC
=CLOSED
FRZ >TEMP
LIMIT
Y1 = ON
TIME > 30
SEC
CON > 0
POWER/ SWITCHES/SENSOR
STATUS CHECK
START
TIMER
NO
YES
NO
YES
NO
YES
T > ASC OR
RS SEC
YES
NO
TIME > 120
SEC
START
TIMER
NO
YES
NO
YES
START
ANTI SHORT CYCLE
INITIAL
POWER UP
YES
NO
START
RANDOM START UP
START
COUNTER
NEEDED?
YES
COUNT = 2
OR
COUNT = 4
BLINK CODE ON STATUS LED
DISPLAY OUTPUT = PULSE
ALR OUTPUT = ON/PULSE
NO
YES
HARD
LOCKOUT?
CC OUTPUT = OFF
V > 18VAC
NO
YES
YES
NO
BLINK CODE
ON STATUS LED
NO
RESET ON
Y
CLEAR FAULTS
R = 24VAC
NO
YES
NO
YES
NO
YES
HPC =
CLOSED
RESET ON R