Status Display5-4
Peripheral bus initialization error: Possible causes for errors are:
Hardware error of an I/O module.
Missing 24 V power supply of the POS-SA 1/2 module.
Module number in the input or output area is given twice.
Invalid bus address: The PROFIBUS-DP address set on the S1 DIP
switch lies outside of the permissible range (valid range: 2-125).
Hardware watchdog active: The hardware watchdog has reacted
because of a fatal system error.
5.3 Alternating Display with Starting Signal F
Display Significance
F
7
Module number
2
Error on image exchange with
I/O module
F
A
Module number
Module number of an input
module lies outside of the
permissible range
i.e. > 47
F
b
Module number
Module number of an output
module lies outside of the
permissible range
i.e. > 47
F
d
Module number
In- and output module have
been given the same module
number.
F
C
Module number
A module is logically located in
the wrong area, i.e.
An output module is logically
located in the input area.
An input module is logically
located in the output area.
An input/output module (I/O)
is logically located only in
the input area or only in the
output area.
The reason is a hardware error
or a firmware error of the
respective module.
F
E
Module number
Peripheral bus module is not
supported
e.g. intelligent module
F
F
Module number
Unknown peripheral bus
module
2
This display is possible in version 211 and higher.