1070 072 449-102 (01.12) GB
Technical Data 9-1
9 Technical Data
Technical Data RM2-DP12 Module
Complies fully with the requirements of IEC1131-2
DIN VDE 0110
DIN EN 60204-1 (as per VDE 0113)
Weight: 270 g approximately
Dimensions (W x H x D): 30 x 182 x 115 mm
Front panel: : Module width 1
Storage temperature: -25...+70°C as per IEC 1131-2
Operating temperature: 0...55°C as per IEC 1131-2
Slot: The module must only be operated on slot 1 in the
mounting rack.
Power Supply: 24 VDC (-15...+20%)
Power failures of up to 10 ms with nominal
voltage, with a 1 s break in between as per
IEC 1131-2.
Current input: 1.35 A max.
Discharge capacity: 24 V against protective earth: 4.7 nF
0 V against protective earth: 4.7 nF
Internal supply for I/O modules: 7.5 V (+/- 5%) / 1.2 A max.
Supply of bus interface (X71):
P5VISO/GNDISO (+/- 5%) / externally 100 mA
max. RS485, electrically isolated.
Degree of protection: IP20 as per DIN VDE 0470-1
incorporated in the housing.
Class of protection:
1 as per VDE 0106 T1 or VDE 0160 (IEC 536)
Insulation test:
350 VAC
500 VDC
Atmospheric pressure: Operation up to 2000 m above sea level as per
IEC 1131-2
Humidity rating: RH-2; 5%...95% as per IEC 1131-2.
F as per DIN 40040
Condensation not permissible.
Corrosion / chemical resistance: The ambient air must be free of elevated concen-
trations of acids, alkali, corrosive agents, salt,
metal vapors or other electrically conductive
pollutants.
Dirt resistance: Degree of contamination 2 as per EN 1131-2
The RM2-DP12 module requires a dustfree
environment. The housing and compartments in
which the mounting rack is located must comply
with the minimum degree of protection IP54 as per
DIN VDE 0470-1.
Transportability: Height of fall in packaging 1.0 m as per IEC 1131-2