easy/easy compact/easy split +030220791 - rel. 3.2 - 13.07.2010
5.8 Table of easy split parameters
Par. Description Type Min Max UOM Def. Visibility
PS password F 0 200 - 22 S,C
/2 probe measurement stability C 1 15 - 4 S,C
/3 probe display rate C 0 15 - 0 S,C
/4 select probe displayed F 1 3 - 1 S,C
/5 select °C/°F C 0 1 - 0 S,C
/6 disable decimal point C 0 1 - 0 S,C
/C1 probe 1 o set F -50 50 (°C/°F) 0 S,C
/C2 probe 2 o set F -50 50 (°C/°F) 0 S,C
/C3 probe 3 o set F -50 50 (°C/°F) 0 S,C
/P select type of probe C 0 1 - 0 S,C
St set point F r1 r2 °C/°F 4 S,C
rd di erential F 0 19 °C/°F 2 S,C
r1 minimum set point value C -50 r2 °C/°F -50 S,C
r2 maximum set point value C r1 300 °C/°F 90 S,C
r3 select direct/reverse operation C 0 2 - 0 S,C
r4 night-time set point delta C -50 +50 °C/°F 3 S,C
c0 compressor and fan start delay on power-up C 0 100 min 0 S,C
c1 minimum time between consecutive compressor starts C 0 100 min 0 S,C
c2 minimum compressor o time C 0 100 min 0 S,C
c3 minimum compressor on time C 0 100 min 0 S,C
c4 compressor on time with duty setting C 0 100 min 0 S,C
cc continuous cycle duration C 0 15 h 4 S,C
c6 temperature alarm bypass after continuous cycle C 0 15 h 2 S,C
c11 second compressor delay C 0 250 s 4 S,C
d0 type of defrost C 0 4 - 0 S,C
dI interval between defrosts F 0 199 h/min
(see dC)
8 S,C
dt end defrost temperature set point/defrost temperature threshold with temp. control F -50 300 °C/°F 4 S,C
dP maximum defrost duration F 1 199 min/s 30 S,C
d4 defrost when switching the instrument on C 0 1 - 0 S,C
d5 defrost delay on power-up or when enabled by digital input C 0 199 min 0 S,C
d6 freeze control temperature display during defrost C 0 1 - 1 S,C
dd dripping time F 0 15 min 2 S,C
d8 alarm bypass time after defrost F 0 15 h 1 S,C
d9 defrost priority over compressor protectors C 0 1 - 0 S,C
d/ defrost probe reading F - - °C/°F - S,C
dC time base C 0 1 - 0 S,C
A0 alarm and fan temperature di erential C -20 20 °C/°F 2 S,C
AL absolute/relative temperature for low temperature alarm F -50 300 °C/°F 0 S,C
AH absolute/relative temperature for high temperature alarm F -50 300 °C/°F 0 S,C
Ad temperature alarm delay C 0 199 min 0 S,C
A4 3rd input con guration C 0 14 - 0 S,C
A7 digital alarm input delay C 0 199 min 0 S,C
A8 enable alarm “Ed” (end defrost by timeout) C 0 1 - 0 S,C
Ac dirty condenser alarm set point C -50 300 °C/°F 70 S,C
AE dirty condenser alarm di erential temperature C 0.1 20.0 °C/°F 5 S,C
Acd dirty condenser alarm delay C 0 250 min 0 S,C
Ado door management algorithm C 0 1 - 0 S,C
F0 enable evaporator fan control C 0 1 - 0 C
F1 evaporator fan control set point F -50 300 °C/°F 5 C
F2 stop evaporator fan if compressor o C 0 2 - 1 C
F3 evaporator fan status during defrost C 0 1 - 1 C
Fd post-dripping time F 0 15 min 1 C
F4 fan ON time (when F2=2) C 0 100 min 5 C
F5 fan OFF time (when F2=2) C 0 100 min 10 C
H0 serial address C 0 207 - 1 S,C
H1 AUX output con guration C 0 7 - 4 S,C
H2 enable keypad C 0 2 - 1 S,C
H4 disable buzzer C 0 1 - 0 S,C
H5 ID code (read-only) F 1 199 - 0 S,C
H6 select control associated with UP + DOWN buttons C 0 1 - 1 S,C
H7 management of fourth relay/serial communication C 0 1 - 1 C
EZY rapid parameter set selection C 0 4 - 0 S,C
tEn enable RTC C 0 1 - 0 S,C (*)
d1d defrost time band 1st day C 0 11 day 0 S,C (*)
d1h time band 1st hour C 0 23 h 0 S,C (*)
d1M time band 1st minutes C 0 59 min 0 S,C (*)
d2d defrost time band 2nd day C 0 11 day 0 S,C (*)
d2h time band 2nd hours C 0 23 h 0 S,C (*)
d2M time band 2nd minutes C 0 59 min 0 S,C (*)
d3d defrost time band 3rd day C 0 11 day 0 S,C (*)
d3h time band 3rd hours C 0 23 h 0 S,C (*)
d3M time band 3rd minutes C 0 59 min 0 S,C (*)
d4d defrost time band 4th day C 0 11 day 0 S,C (*)
d4h time band 4th hours C 0 23 h 0 S,C (*)
d4M time band 4th minutes C 0 59 min 0 S,C (*)
nOd night time band ON day C 0 11 day 0 S,C (*)
nOh night time band ON hours C 0 23 h 0 S,C (*)
nOM night time band ON minutes C 0 59 min 0 S,C (*)
nFd night time band OFF day C 0 11 day 0 S,C (*)