14
GB
easy way ARIA +030220841 - rel. 1.0 - 26.10.2007
Terminal
Important: The following procedure reinitialises the terminal
and removes the connection to the reference access point. Access
in the parameter programming procedure and set loc21 = ON (see
paragraph 4.5).
Parameter loc21 is used to return the terminal to the default con guration
(including the supervisor address).
par. description min max def UOM type index R/W notes
loc 21
Reset to manufacturer defaults
0 no e ect
1 perform reset to manufacturer defaults
0 1 0 - - - R/W
password
access
3.6 Wireless variables
The variables that de ne the function of an END DEVICE in ZigBee
communication are as follows:
Minimum supervisor transmission time
The devices (terminal and sensor), in order to ensure a battery life of at
least a few years, cannot transmit continually to the access point.
These devices are normally “sleeping” and “wake up every ‘n minutes
(where ‘n is decided by the user based on the application).
Battery level:
Indicates the current charge of the battery on the terminal/sensor. This
mainly depends on the time set between transmissions and the time
the keypad/display is used (terminal only).
In normal operating conditions, the following table shows the typical
battery life according to the time set between transmissions.
transmission time
terminal battery life
in years
sensor battery life in
years
123
535
10 5 8
15 8 8
Tab. 3.e
Note: if the device does not communicate correctly with the
access point (problems of distance, interference,…) the battery life
may be reduced.
Wireless signal level
This indicates the strength of the wireless signal for communication
between the terminal/sensor and the nearest access point/repeater.
-100dBm = poor signal
-30dBm = strong signal
Terminal and sensor supervisor variables
par. description min max def UOM type index R/W notes
- Battery level 0.0 100.0 -- % A 3 R
-
-
Indicative wireless signal level -100.0 -30.0
-
Dbm A 8 R
-
- Minimum supervisor transmission time 1 60 2 min I 28 R/W
-
Tab. 3.f