6 – APPLICATION DATA
6.1 – Cooling operating range
6.2 – Heating operating range
Operating Range
Cooling mode
Evaporator Min.temperature Max.temperature
Entering water temperature (at start) ℃ - 45
Entering water temperature (during operation) ℃ 6.8 21
Entering water temperature (during stop) ℃ 3 55
Leaving water temperature (during operation)℃ 4 15
Condenser Min.temperature Max.temperature
Outdoor air temperature -10 46
* A glycol/water solution must be used if the air temperature is below 0°C,
** Max 50°C during part load operation;
Lengend
Part load
Operating range, standard unit.
Below 0°C air temperature the unit must either be equipped with the
evaporator frost protection option (41A or 41B), or the water loop must be
protected against frost by using a frost protection solution by the installer