42 Carrier Yileng - Shanghai, China
General visual inspection for any signs of deterioration.
10.2 - Level 2 maintenance (see note)
This level requires specific know-how in the electrical, hydronic and mechanical fields. It is possible that these
skills are available locally: existence of a maintenance service, industrial site, specialized subcontractor. In these
cases, the following maintenance operations are recommended. Carry out all level 1 operations, then:
At least once a year tighten the power circuit electrical connections (see tightening torques table).
Check and re-tighten all control/command connections, if required (see tightening torques table).
• Remove the dust and clean the interior of the control boxes, if required.
• Check the presence and the condition of the electrical protection devices.
• Check the correct operation of all heaters.
• Replace the fuses every 3 years or every 15000 hours
• Check the height of the anti-vibration mountings (located between the compressor rails and the unit chassis) after
5 years of operation, and then each year. When the total minimum height of the mountings is less than 28 mm
replace the mountings.
Check the water connections.
Purge the water circuit (see chapter Water flow control procedure).
Clean the water filter (see chapter Water flow control procedure).
Fully clean the condensers with a low-pressure jet and a bio-degradable cleaner (counter-current cleaning -see
chapter Condenser coil - level 2).
Replace the stuffing box packing of the pump after 10000 hours of operation.
Check the unit operating parameters and compare them with previous values.
Keep and maintain a maintenance sheet, attached to each HVAC unit.
All these operations require strict observation of adequate safety measures: individual protection garments,
compliance with all industry regulations, compliance with applicable local regulations and using common sense.
10.3 - Level 3 (or higher) maintenance (see note)
The maintenance at this level requires specific skills/ approval/tools and know-how and only the manufacturer, his
representative or authorized agent are permitted to carry out these operations. These maintenance operations
concern for example:
A major component replacement (compressor, evaporator)
Any intervention on the refrigerant circuit (handling refrigerant)
Changing of parameters set at the factory (application change)
Removal or dismantling of the HVAC unit
Any intervention due to a missed established maintenance operation
Any intervention covered by the warranty
NOTE: Any deviation or non-observation of these maintenance criteria will render the guarantee conditions
for the HVAC unit nul and void, and the manufacturer, Carrier will no longer be held responsible.
10.4 - Tightening torques for the main electrical connections
Component
Designation
in the unit
Value
(Nm)
Screw on bus bar, customer connection
M8
18
M10
L1/L2/L3
30
Soldered screw PE, customer connection(M12)
PE
70
Tunnel terminal screw, compressor contactor
Contactor 3RT504_
5
Contactor 3RT505_
11
Contactor 3RT506_
KM
21
Tunnel terminal screw, current transformer
Size 2 (3RB2956)
11
Size 3 (3RB2966)
TI
21

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier AquaForce 30XQ0502 and is the answer not in the manual?

Carrier AquaForce 30XQ0502 Specifications

General IconGeneral
BrandCarrier
ModelAquaForce 30XQ0502
CategoryChiller
LanguageEnglish

Related product manuals