About Requirements for Perforated Cabinets
A perforated cabinet has perforations in its front and rear doors and side walls. In addition to the requirements
listed in the “General Requirements for Cabinets and Racks” section, perforated cabinets must meet the
following requirements:
The front and rear doors must have at least a 60-percent open area perforation pattern, with at least 15
square inches (96.8 square cm) of open area per rack unit of door height.
The roof should be perforated with at least a 20-percent open area.
The cabinet floor should be open or perforated to enhance cooling.
The Cisco R Series rack conforms to these requirements.
About Requirements for Open Racks
In addition to the requirements listed in the “General Requirements for Cabinets and Racks” section on page
A-1, if you are mounting the chassis in an open rack (no side panels or doors), ensure that the rack meets the
following requirements:
The minimum vertical rack space per chassis must be two rack units (RU), equal to 3.47 inches (8.8 cm).
The horizontal distance between the chassis and any adjacent chassis should be 6 inches (15.2 cm), and
the distance between the chassis air vents and any walls should be 2.5 inches (6.4 cm).
Cisco Nexus 3500 Hardware Installation Guide
36
Rack Specifications
About Requirements for Perforated Cabinets

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco Nexus 3500 and is the answer not in the manual?

Cisco Nexus 3500 Specifications

General IconGeneral
BrandCisco
ModelNexus 3500
CategorySwitch
LanguageEnglish

Related product manuals