23
7 - START-UP
The T_SA supply setpoint is calculated in relation to the SPR return setpoint.
Set the values related to the T_SA supply air setpoint in relation to the T_RA return temperature:
Main index \ Parameter machine \ Thermoregulator
P0070 LimMinSupplyT
P0071 LimMaxSupplyT
P0072 MC_BandPr
P0073 MC_DeadBand
Humidity setpoint
Main index \ Parameter machine \ Plant config
set the specific supply humidity setpoint in cooling mode: P0017 SetXSA
set the specific return humidity setpoint in heating mode: P0018 SetXSR
Confirm configuration
Main index \ Parameter machine \ Plant config
set P0020 ConfirmConf = Yes